Payne PA1Z Installation, Start-Up And Service Instructions Manual page 15

Packaged air conditioners
Table of Contents

Advertisement

UNIT
MOTOR
PA1Z
SPEED
DELIVERY
Low
024
Med
High
Low
030
Med
High
Low
036
Med
High
Low
042
Med
High
Low
048
High
Low
060†
Med
High
*Air delivery values are based on operating voltage of 230 v or 460 v,
dry coil, without filter or electric heater. Deduct wet coil, filter, and elec-
tric heater pressure drops to obtain external static pressure available
for ducting. See Tables 5-7.
†460-v motors have 2 speeds (size 060 only).
Table 5 — Wet Coil Pressure Drop
UNIT SIZE
AIRFLOW
PA1Z
(cfm)
600
700
024
800
900
900
030
1000
1200
1000
1200
036
1400
1600
1000
1200
042
1400
1600
1400
048
1600
1800
1700
1800
060
2100
2300
Table 4 — Dry Coil Air Delivery* — Horizontal Discharge
(Deduct 10% for 208 Volt Operation)
AIR
0.1
0.2
Watts
288
285
CFM
875
820
Watts
390
383
CFM
1131
1090
Watts
528
520
CFM
1391
1338
Watts
288
285
CFM
875
820
Watts
390
383
CFM
1131
1090
Watts
528
520
CFM
1891
1338
Watts
450
435
CFM
1231
1218
Watts
470
450
CFM
1302
1264
Watts
660
635
CFM
1700
1660
Watts
478
458
CFM
1303
1270
Watts
481
468
CFM
1310
1280
Watts
798
CFM
1736
Watts
CFM
Watts
CFM
Watts
890
850
CFM
1834
1820
Watts
1040
1018
CFM
2230
2102
Watts
1073
1038
CFM
2230
2202
PRESSURE DROP
(in. wg)
0.02
0.05
0.06
0.07
0.06
0.06
0.08
0.07
0.09
0.11
0.12
0.04
0.06
0.08
0.09
0.07
0.08
0.09
0.07
0.08
0.09
0.10
230 AND 460 VOLT HORIZONTAL DISCHARGE
External Static Pressure (in. wg)
0.3
0.4
0.5
282
279
274
802
734
668
378
369
360
1038
978
917
510
495
480
1285
1200
1115
282
279
274
802
734
668
378
369
360
1038
978
917
510
495
480
1285
1200
1115
420
400
380
1204
1120
1008
445
410
388
1205
1163
1081
610
575
540
1581
1450
1297
440
411
378
1224
1179
1126
450
438
404
1241
1181
1110
678
647
618
1688
1618
1510
801
760
730
1898
1841
1757
870
842
818
2000
1903
1799
810
790
735
1791
1762
1703
1000
950
890
2025
1960
1901
1001
958
896
2160
2122
2052
NOTES:
1. Do not operate the unit at a cooling airflow that is less than 350 cfm
for each 12,000 Btuh of rated cooling capacity. Evaporator-coil frost-
ing may occur at airflows below this point.
2. Dashes indicate portions of the table that are beyond the blower
motor capacity or are not recommended.
Table 6 — Filter Pressure Drop (in. wg)
FILTER
UNIT SIZE
SIZE
PA1Z
(in.)
024-042
24 × 24 0.06 0.07 0.08 0.08 0.09
048,060
24 × 30
FILTER
UNIT SIZE
SIZE
PA1Z
(in.)
024-042
24 × 24 0.10
048,060
24 × 30
FILTER
UNIT SIZE
SIZE
PA1Z
1900 2000 2100 2200 2300
(in.)
024-042
24 × 24
048,060
24 × 30 0.14 0.15 0.16 0.17 0.18
—15—
0.6
0.7
0.8
268
261
582
478
350
340
830
721
460
450
1018
920
268
261
582
478
350
340
830
721
460
450
1018
920
335
326
311
950
863
751
359
338
321
940
873
783
505
485
460
1190
1095
989
350
327
317
1022
911
816
370
338
320
1022
943
811
578
540
500
1421
1309
1187
688
650
600
1682
1564
1429
782
696
632
1718
1625
1446
680
580
480
1640
1415
1159
835
790
650
1855
1752
1468
840
800
691
1926
1791
1588
CFM
500
600
700
800
900
CFM
1200 1300 1400 1500 1600 1700 1800
0.11
0.12 0.14
0.15
0.08
0.09
0.10
0.11
CFM
0.9
460
1060
570
1365
628
1333
422
950
580
1121
575
1202
1000 1100
0.09
0.09
0.12 0.13