4 INSTALLATION

The installation of the AMC-VersaTox is very important as the operational quality is a direct
result of the quality of the installation. The following sections provide guidelines for installation;
location and mounting, wiring, and cable selection.

4.1 LOCATION AND MOUNTING

Mount the AMC-VersaTox sensor/transmitter on a solid, non-vibrating surface or structure in an
area where the ambient concentration of gas is not directly affected by the presence of clean air
supply, ventilation systems, or blockage by surrounding articles and sources of interference
gases. Please, refer to local codes for sensor/transmitter installation information. The installer is
required to provide any mounting hardware that may be required. The AMC-VersaTox
sensor/transmitter circuit board(s) with sensor is removable from the enclosure for ease of
installation.
Notes:
Mount enclosure with the sensor located as shown is Figure 4-1 and Figure 4-2. This
will ensure correct orientation. Where possible it is recommended to turn off supply
power before removing or replacing the transmitter or sensor.

4.1.1 CONDUIT MOUNTING

1/2" Ø CONDUIT
0.75"
2.13"
AMC VersaTox
www.armstrongmonitoring.com
1-800-465-5777
3156502A
TRANSMITTER
3.80"
Figure 4-1 Conduit Mounting
11
SENSOR
3.62"