Commissioning; Preliminary Checks; Powering The Idr-M Mimic; Idr Configuration Tool - Honeywell NOTIFIER IDR-M Installation And Commissioning Manual

Table of Contents

Advertisement

IDR-M Mimic Installation & Commissioning Manual
Only terminate the IDR-M
mimic power cables at the
control panel after ALL
preliminary checks have
been done.
Only connect power
cables when the
system power is OFF.
Static Sensitive Devices!
Use anti-static wrist strap
when carrying out this
procedure
3

Commissioning

This section describes the procedure for
commissioning the IDR-M mimic components.

3.1 Preliminary Checks

Carry out the following preliminary checks for
EVERY IDR-M mimic being commissioned, prior
to powering-up the system:
1 Check that all cables brought into the
IDR-M mimic have been terminated
correctly. The connection of external wiring
is described in Section 2.5.1.1. All power
and signal cabling and wiring must conform
to the appropriate local regulation.
2 Ensure that all the IDR-M mimic
components have been correctly re-
installed within the enclosure.
3 Check that the mimic address has been set
as described in Section 2.5.1.2.
4 Check that the DIP switch on the IDR-MD
Mimic Driver board has been set correctly,
and that all jumper links are configured
correctly, as described in Section 2.5.2.1.

3.2 Powering the IDR-M Mimic

The IDR-M mimic obtains 18-32V and 0V dc
supplies either from the fire control panel
auxiliary outputs or, depending upon the IDR-M
mimic drive requirements, from a local
independent power supply. Connections are
made as described in Sections 2.4 and 2.5.1.
Caution: Do not remove power from a
networked IDR-M mimic while the system
is still working.

3.3 IDR Configuration Tool

This Tool configures the IDR-M mimic with
Rules which relate its outputs (output channel
LEDs/relays and I/O relays) to defined events.
There are three types of Rules:
a. Board Rules - similar to using the Mimic
Driver Board DIP switch, but allows
individual zone selections for each board.
b. Zone Rules.
c. Loop, panel or device-dependent Rules.
When these Rules have been downloaded into
the IDR-M mimic they override the selections
made on the Mimic Driver Board DIP switch.
The Tool is supplied with a help document
(Acrobat PDF format) which describes its use.
17