CHINT NXZ Series User Instructions page 10

Automatic transfer switch
Table of Contents

Advertisement

1. Any form of electrical connection is prohibited between the two groups of terminals; otherwise it may result in the burn-out of controller!
2. Terminals 401 and 402 of type A and type B controllers can be connected with passive closing signal only to achieve fire control
linkage. If they are directly connected to any active signal, the controller will be burnt out.
5
Installation of Isolation Padlock
Indication of normal state
The product is in the state. Move the orange button
the manual position.
Pull out the limiting piece and lock it.
Figure 10
Installation of isolation padlock
08
NXZ Automatic Transfer Switch
Indication of alternative state
to