Amplifier Specifications

The specifications below apply to both analog and digital amplifiers.
Specifications
Supply voltage:
Output voltage:
Maximum output power:
Flex-50
Alarm state:
Supervision state:
Low power state
Flex-35
Alarm state:
Supervision state:
Low power state
The equipment operates normally with ambient temperatures outside the cabinet from 32° to
120° F (0° to 49° C), inclusive.
The equipment operates normally under non-condensing humidity conditions up to 93% relative
humidity at 90° F (32° C).
19.7-31.1 VDC
25 VRMS or 70.7 VRMS
Flex-35 = 35 W; Flex-50 = 50 W
5.55 A (signal)
351 mA (signal)
(NACs in supervision, no power to power stage):
0 A (signal)
4.00 A (signal)
351 mA (signal)
(NACs in supervision, no power to power stage):
0 A (signal)
firealarmresources.com
74 mA (card)
74 mA (card)
85 mA (card)
74 mA (card)
74 mA (card)
85 mA (card)