Standard Modbus Default Settings - Trane E50 Series Installation, Operation And Maintenance Manual

Compact power and energy meter
Table of Contents

Advertisement

Standard Modbus Default Settings

Setting
Setup Password
Reset Password
System Type
CT Primary Ratio (only if CTs are not
included)
CT Secondary Ratio
PT Ratio
System Voltage
Maximum Theoretical Power (Analog
Output: Full Scale (20 mA or 5 V)
Display Mode
Phase Loss
Pulse Energy
Demand: Number of Sub-intervals
per interval)
Demand: Sub-interval Length
Modbus Address
Modbus Baud Rate
Modbus Parity
24
Value
00000
00000
40 (3+N) Wye
100 amp
1 volt
1:1 (none)
600 V L-L
104 kW
1 (IEEE)
10% of system voltage (60 volt),
25% Phase-to-Phase Imbalance`
1 (kWh/pulse)
1 (block mode)
900 sec (15 min)
001
19200 baud
None
Modbus Register
130
131
132
133
134
135
137
142, 143
144
149
150
BAS-SVX073C-EN