Trane E50 Series Installation, Operation And Maintenance Manual page 6

Compact power and energy meter
Table of Contents

Advertisement

P P r r o o d d u u c c t t I I d d e e n n t t i i f f i i c c a a t t i i o o n n , , S S p p e e c c i i f f i i c c a a t t i i o o n n s s , , a a n n d d D D a a t t a a O O u u t t p p u u t t s s
Mechanical Characteristics:
IP40 Degree of Protection (IEC60529):
Operating Conditions:
Agency Compliance
Data Outputs (Modbus Only)
6
Weight:
Display Characteristics:
Terminal Block Screw Torque:
Terminal Block Wire Size:
Rail:
Operating Temp:
Storage Temp:
Humidity Range:
Altitude of Operation:
U.S. and Canada:
CE:
Dielectric Withstand:
Conducted/Radiated Emissions:
Conducted/Radiated Immunity:
U.S./Canada (cULus)
Europe (CE):
Full Data Set:
0.62 LB. (0.28 kg)
IP40 front display; IP20 Meter
Backlit blue LCD
0.37 ft-lb (0.5 N·m) nominal/0.44 ft-lb (0.6 N·m) maximum
24 AWG to 14 AWG (0.2 to 2.1 mm2)
T35 (35 mm) DIN Rail per EN50022
-30°C to 70°C (-22°F to 158°F)
-40° to 85°C (-40° to 185°F)
<95% RH (non-condensing)
3000 m
CAT III;
Pollution Degree 2
For distribution systems up to 347 V
CAT III;
Pollution Degree 2
For distribution systems up to 300 V
Per U.L. 508, EN61010
FCC part 15 Class B, EN55011/EN61000 Class B (residential and
light industrial)
U.L. EN61000 Class A (heavy industrial)
U.L. 508 (open type device)/CSA 22.2 No. 14-05
U.L. EN61010-1
Power (kW), Energy (kWh)
Configurable for CT & PT ratios, system type, and passwords
Diagnostic alerts
Current/Volts are both 3-phase average
Current by phase and volts by phase Line-Line and Line-
Neutral
Power: Real, reactive, and apparent 3-phase total and per
phase
Power factor: 3-phase average and per phase
Frequency
Power demand: most recent and peak
Demand configuration: fixed, rolling block, and external
sync
/600 Vac
L-N
L-L
L-N
BAS-SVX073C-EN