Standard BACnet Default Settings

Setting
Setup Password
Reset Password
System Type
CT Primary Ratio
PT Ratio
System Voltage
Maximum Theoretical Power
Display Mode
Phase Loss Voltage Threshold
Demand: Number of sub-intervals
length
Demand: Sub-interval Length
BACnet MAC Address
BACnet TP Baud Rate
BACnet TP Max_Requestor
BACnet Device_ID
BACnet Device Location
(a)
24
Default values are preset at the factory. Once changed, defaults can no longer be automatically reset- they must be restored
individually. The baud rate and MAC address are set through the user-interface screens, and all other values are set by re-
writing each Object.
Default Values
(a)
00000
00000
40 (3+N) Wye
100 amp
1:1 (none)
600 V L-L
Calculated from AV2, AV3, AV4,
AV5, and AV6 (with default settings,
power is 103.92 kW
1 (IEEE)
10% of system voltage
25% phase-to-phase imbalance
1 (block mode)
900 sec (15 min)- AV11 default
value is 90000 [1/100 seconds]
001
76.8 kBaud
127
Pseudo-random value from
1,000,000 to 3,097,151
Installed location not yet identified
BACnet Object
AV2
AV3
AV5
AV6
AI45
AV7
AV8
AV9
AV10
AV11
Device
Device
Device
BAS-SVX076C-EN