Product Identification, Specifications, and Data Outputs

Product Identification
Measurement Accuracy
Input Voltage Characteristics:
Input Current Characteristics
Control Power
External DC current limiting is required.
Output
BAS-SVX073C-EN
Model:
Description:
Output:
Real Power and Energy:
Reactive Power and Energy:
Current:
Voltage:
Sample Rate:
Data Update Rate:
Type of Measurement:
Measured AC Voltage:
Metering Over Range:
Impedance:
Frequency Range:
CT Scaling:
Measurement Input Range:
Impedance:
AC:
DC:
Ride-through Time:
Alarm Contacts:
Real Energy Pulse Contacts:
RS-485 Port:
E50C2-T2
Modbus output, full data set
Pulse, RS-485, Alarm
IEC 62053-22 Class 0.2S, ANSI C12.20 0.2%
IEC 62053-23 Class 2, 2%
0.4% (+0.015% per °C deviation from 25°C) from 5% to 100%
of range; 0.8% (+0.015% per °C deviation from 25°C) from 1%
to 5% of range
0.4% (+0.015% per °C deviation from 25°C) from 90 V
600 Vac
L-L
2520 samples per second
1 sec
True RMS up to the 21st harmonic 60 Hz; One to three phase AC
system
Minimum 90 V
(156 V
L-N
L-L
U.L. Maximum: 600 V
(347 V
L-L
CE Maximum: 300V
L-N
+20%
2.5M Ω
/5M Ω
L-N
L-L
45 Hz to 65 Hz
Primary:adjustable from 5 A to 32,000 A
0 Vac to 0.333 Vac or 1 Vac to 1.0 Vac (+20% over range), rated
for use with Class 1 voltage inputs
10.6kΩ(1/3 V mode) or 32.1kΩ (1 V mode)
5 VA max.; 90 V min.
U.L. Maximum: 600 V
(347 V
L-L
CE Maximum: 300V
L-N
3 W maximum
U.L and CE: 125 VDC to 300 VDC
100 milliseconds at 120 Vac
N.C., static output (30 Vac/DC, 100 mA maximm @ 25°C, derate
0.56 mA per °C above 25°C)
N.O., static output (30 Vac/DC, 100 mA maximum @ 25°C,
derate 0.56 mA per °C above 25°C)
2-wire, 1200 to 38400 baud, Modbus RTU
to
L-N
) for stated accuracy
)
L-N
)
L-N
5