Alarm or Condition
1 beep every 5 seconds.
Powerware
5125 Tower (1000–2200 VA) User's Guide
®
Possible Cause
Action
The UPS is running on
Correct the input voltage, if possible. The UPS
battery power because the
continues to operate on battery until the condition is
input voltage is too high or
corrected or the battery is completely discharged.
too low.
If the condition persists, the input voltage in your area
may differ from the UPS nominal.
The utility line voltage and
Have a qualified electrician check the wiring.
frequency are out of
specification.
The battery may be fully
Plug the UPS into a power outlet for 24 hours to charge
discharged.
the battery. After charging the battery, press and hold
the
indicator.
If the
on page 33 to replace the battery.
The battery is not
Check the battery connections. Call your service
connected correctly.
representative if the problem persists.
Rev B www.powerware.com
S
Troubleshooting
button for 3 seconds; then check the
indicator is still on, see "UPS Maintenance"
45