Table 6. Environmental and Safety
Operating Temperature
Storage Temperature
Transit Temperature
Relative Humidity
Operating Altitude
Transit Altitude
Audible Noise
Surge Suppression
Safety Conformance
Agency Markings
EMC
Table 7. Battery
Configuration
1000 VA: (2) 24V, 9 Ah internal batteries
1500 VA: (4) 48V, 7 Ah internal batteries
2200 VA: (4) 48V, 12 Ah internal batteries
EBM Configuration
PW5125 EBM-24: (8) 24V, 9 Ah batteries
PW5125 EBM-48: (8) 48V, 9 Ah batteries
Type
Sealed, maintenance-free, valve-regulated, lead-acid
Charging
Internal battery: less than 3 hours to 90% usable capacity at nominal line voltage after full
load discharge
External battery: recharging at 80% load or less is recommended; no more than 16x discharge
time to 90% usable capacity at nominal line voltage after full load discharge; an external
battery charger is recommended for faster recharge times when using more than 2 EBM
Monitoring
Advanced monitoring for earlier failure detection and warning; auto detection of additional
EBMs
Powerware
5125 Tower (1000–2200 VA) User's Guide
®
Low Voltage Models
10°C to 40°C (50°F to 104°F)
Optimal battery performance: 25°C (77°F)
0°C to 25°C (32°F to 77°F)
-25°C to 55°C (-13°F to 131°F)
5–95% noncondensing
Up to 3,000 meters above sea level
Up to 15,000 meters above sea level
Less than 40 dBA Normal mode, typical load
Less than 55 dBA Battery mode
ANSI C62.41 Category B (formerly IEEE 587), IEC 61000-4-5
UL 1778, UL 497A;
CAN/CSA C22.2, No. 107.1;
NOM-019-SCFI
UL, cUL, NOM
FCC Part 15, ICES-003, VCCI
Rev B www.powerware.com
S
Specifications
High Voltage Models
UL 1778, UL 497A (data line only);
CAN/CSA C22.2, No. 107.1;
EN 50091-1-1 and IEC 60950
UL and cUL; CE, C-Tick, LGA/GS, DEMKO
EN 50091-2, FCC Part 15, ICES-003
s.