Unitronics CP1 Manual page 8

Table of Contents

Advertisement

The second line of the display will identify the nature of the alarm.
Auto Reset
Check Photo Eye -
Warning
Compactor 80%
"1" To Reset Low Oil Level
"1" To Reset Compactor Full
"1" To Reset Transducer Error
Auto Reset
Access Door Open
Auto Reset
Motor Overload
Auto Reset
Oil Cool Down
Auto Reset
Container Away
Auto Reset
Through Door
If more than one alarm is present the screen will scroll though all active alarms. The UP ARROW key will
return the operator to the startup screen.
Auto Reset
The photo eye has not seen its reflector for more than 30 minutes.
Check alignment and clean both reflector and photo eye. To prevent
overheating the oil or the directional valve solenoid the alarm will shut
the compactor down for 10 minutes. After this cool down the system will
automatically restart.
Early warning – Garbage bin is getting full. This alarm will not stop the
compactor. It can be reset by pressing the "1" Reset Alarm key. Or if left
unattended will change to a COMPACTOR FULL alarm when the
compactor is full.
Refill reservoir with AW 32 oil.
Replace the container
Either the transducer cable has been cut or the transducer has failed.
As this alarm will clear automatically after the door is reclosed.
The pump motor starter has tripper because of a current overload.
Press the blue reset button on the overload to reset alarm.
Oil temperature has exceeded 185 degrees. The Compactor will shut
down and automatically restart at the end of a 15 minute shutdown.
period. If the oil has cooled, the time can be aborted by pressing the "1"
Reset key.
The compactor does not have a container attached.
The door mounted to the compactor is open or not aligned
alarm must clear, and the operator must acknowledge this
alarm, "1", before the compactor will run.
This alarm will clear automatically.