Table 2 shows the System Settings for the HLU-200 List 1E.
Mode
Selection
ZBTS
ON
OFF*
ESAL
17
170
NONE*
LBTO
NONE
20
60*
120
ALM
DIS
ENA*
LPBK
DIS
ENA*
HLU-200 List 1E
ETTINGS
Table 2. System Settings
Description
The HiGain system is in the ESF frame and is operating in
its Zero-Byte Timeslot Interchange (ZBTSI) mode.
The HiGain system is in the ESF frame and is operating in
its normal non ZBTSI mode.
Activates the alarm input signal to the LITESPAN
microprocessor and flashes the red Status LED when 17
Errored Seconds (ES) (17 HDSL CRC errors on either HDSL
loop or a total of 17 BPVs and FERR) occur within a 24-hour
period.
Activates the alarm input signal to the LITESPAN
microprocessor and flashes the red Status LED when 170
Errored Seconds (ES) (170 HDSL CRC errors on either
HDSL loop or a total of 170 BPVs and FERR) occur within a
24-hour period.
Prevents the generation of an alarm due to excessive
Errored Seconds.
Disables automatic time-out cancellation of all loopbacks.
Sets automatic cancellation of all loopbacks to 20 minutes
after initiation.
Sets automatic cancellation of all loopbacks to 60 minutes
after initiation.
Sets automatic cancellation of all loopbacks to 120 minutes
after initiation.
Disables the Alarm input signal to the LITESPAN processor
from the HLU processor. The HDSL LED still flashes Red for
an alarm condition even when ALM DIS option is chosen.
Enables activation of the system alarm input signal to the
LITESPAN processor from the HLU processor.
Configures the HLU-200 to ignore the 2 in 5 SmartJack
loopback command.
Enables the HLU-200 to respond to the 2 in 5 SmartJack
loopback command.
September 25, 1998
Using the Maintenance Terminal
9