Refrigerant Type

CSHD and CSHN/CSHL compressors are approved for use
with R-410A refrigerant only. Any use of hydrocarbon
refrigerants or air is strictly prohibited!
Transportation, Handling, and
Storage
The compressor must be handled in the vertical position
(maximum 15-degree offset from vertical). Should the
compressor be handled in an upside down position, its
suitability for its use can not be guaranteed.
NOTICE
Improper Handling!
Improper handling of the compressor resulting from
being handled or transported in the upside position,
dropped or tipped over could result in internal damage to
the compressor and it is recommended that the
compressor not be put into service.
Damage to compressor or packaging should be reported
to the shipper immediately.
Use a proper method of lifting the compressor, both lifting
ears must be used with a spreader bar.
COM-SVN01D-EN
R410A Operating Map - Superheat 20
-10
0
10
Evaporating temperature (°F)
R410A Operating Map - Superheat
F
°
20
30
Heavy Object!
Failure to follow instructions below could result in unit
dropping which could result in death or serious injury,
and equipment or property-only damage. Ensure that all
the lifting equipment used is properly rated for the
weight of the unit being lifted. Each of the cables (chains
or slings), hooks, and shackles used to lift the unit must
be capable of supporting the entire weight of the unit.
Lifting cables (chains or slings) may not be of the same
length. Adjust as necessary for even unit lift.
For approximate compressor weight, see
Spreader bar use is recommended to better balance the
compressor.
General Information
40
50
60
WARNING
Table
70
3.
9