Charging the System

WARNING
Hazardous Pressures!
Failure to follow instructions below could result in a
violent explosion, which could result in death or serious
injury.
If a heat source is required to raise the tank pressure
during removal of refrigerant from cylinders, use only
warm water or heat blankets to raise the tank
temperature. Do not exceed a temperature of 150°F. Do
not under any circumstances apply direct flame to any
portion of the cylinder.
Use R-410A refrigerant only! Follow the instructions in the
unit Installation, Operation, and Maintenance manual (see
"Literature Referenced," p.
methods.
If there are no instructions available, use these guidelines:
Evacuate the unit as described in
Evacuation," p.
18.
Ensure that the oil level is at least 1/2-sight glass in the
compressor
Do not use the compressor to pull refrigerant into the
system.
Charge liquid refrigerant into the high-side of the
unit—either into the condenser or liquid receiver, if so
equipped.
Charge as much of the unit refrigerant charge as
possible before starting the compressor.
Do not charge liquid refrigerant into the low side of the
compressor without the compressor running. Small
amounts of liquid may be metered through refrigerant
gauges into the suction line while the compressor is
operating.
If the unit is equipped with suction and discharge
service valves, close them during the charging
procedure.
Water chiller units—Always operate the chilled water
pumps while charging the unit to prevent freezing the
evaporator.

Verification Before Start-Up

Follow the instructions in the unit Installation, Operation,
and Maintenance manual (see
p.
6). If there are no instructions available, use these
guidelines:
Before starting the unit, verify that all service valves are
open.
Energize the crankcase heater a minimum of 8 hours
before starting the compressor
COM-SVN01D-EN
6) for proper charging
"Vacuum Testing and
"Literature Referenced,"
NOTICE
Improper Crankcase Heater Operation!
Exception to the 8-hour minimum crankcase heater
operation time.
Apply power to the crankcase heater for a minimum of
8 hours prior to startup of the compressor! Failure to
follow this instruction could result in a compressor
failure.
If the compressor is a replacement for a failed compressor
and has been charged in accordance with either the
procedures in the unit IOM or
in this manual, the compressor could be immediately
started after charging the system. The reason for this is
that the refrigerant has not had sufficient time to migrate
to the compressor and cause potential damage upon
startup. The system should set for no more 8 hours or
overnight with a refrigerant charge without crankcase
heater operation. If the time exceeds 8 hours or the unit
sits overnight, the crankcase heater must be operational
for a minimum of 8 hours prior to starting the compressor.
If liquid refrigerant was charged into the suction or low
side during the charging procedure, damage could still
occur.
Removal and Installation
"Charging the System," p. 19
19