Pre-Installation Inspections - Trane CSHD Installation Instructions Manual

Table of Contents

Advertisement

General Information
Figure 3.
Lifting compressor with spreader bar
Use lifting hooks with close clasps.
Table 3.
Compressor weight with full oil charge
Model
CSHD 075 - 092
CSHD 103 - 125
CSHD 136 - 161
CSHD 175/183
CSHN 176 - 250
CSHN315
CSHN374/CSHL374
The compressor and its packaging must not be exposed to
rain and/or corrosive, flammable atmosphere.
The compressor must not be stored in an environment less
than -31°F (-35°C) or to exceed +160°F (+71°C).

Pre-Installation Inspections

Check the following before using the compressor:
Compressor for visible shipping damage.
Compressor is the correct model/part number.
Compressor is the correct voltage.
Compressor ship-with items:
– Restrictors for use with tandem and trio
compressors.
– Oil equalizer Teflon
10
Weight (lb)
128
142
150
160
236
337
362
®
gaskets.
WARNING
R-410A Refrigerant under Higher Pressure
than R-22!
Failure to use proper equipment or components as
described below, could result in equipment failing and
possibly exploding, which could result in death, serious
injury, or equipment damage.
The units described in this manual use R-410A
refrigerant which operates at higher pressures than R-
22. Use ONLY R-410A rated service equipment or
components with these units. For specific handling
concerns with R- 410A, please contact your local Trane
representative.
Figure 4.
Model CSHN/CSHL
Figure 5.
Model CSHD
Oil equalizer rotolock
connection fitting
Oil valve with
dip tube
Oil equalizer rotolock
connection fitting
1/4 Schrader port
COM-SVN01D-EN

Advertisement

Table of Contents
loading

This manual is also suitable for:

CshnCshl

Table of Contents