General Information; Product Code And Functions - flowair EX LITE Technical Documentation Operation Manual

Table of Contents

Advertisement

Available languages

Available languages

1. GENERAL INFORMATION

1.1. PRODUCT CODE AND FUNCTIONS

Dedicated control system for LEO EX heaters located in EX zones. Versions:
EX LITE-1 - control cabinet mounted outside EX zone for LEO EX heater (1pc.), junction box dedicated for EX zone
included (1pc.).
EX LITE-2 - control cabinet mounted outside EX zone for LEO EX heater (2pcs.), junction box dedicated for EX zone
included (2pcs.).
EX LITE-3 - control cabinet mounted outside EX zone for LEO EX heater (3pcs.), junction box dedicated for EX zone
included (3pcs.).
EX LITE-4 - control cabinet mounted outside EX zone for LEO EX heater (4pcs.), junction box dedicated for EX zone
included (4pcs.).
EX PLUS-1 - control cabinet mounted outside EX zone for LEO EX heater (1pc.), junction box dedicated for EX zone
(1pc.) and thermostat for EX zone (1pc.).
EX PLUS-2 - control cabinet mounted outside EX zone for LEO EX heater (2pcs.), junction box dedicated for EX
zone (2pcs.) and thermostat for EX zone (1pc.).
EX PLUS-3 - control cabinet mounted outside EX zone for LEO EX heater (3pcs.), junction box dedicated for EX
zone (3pcs.) and thermostat for EX zone (1pc.).
EX PLUS-4 - control cabinet mounted outside EX zone for LEO EX heater (4pcs.), junction box dedicated for EX
zone (4pcs.) and thermostat for EX zone (1pc.).
EX LITE features:
START-STOP rotary switch
phase asymmetry, sequence, failure detection
overcurrent and short-circuit motor protection
thermistor motor protection relay MSR220VA (ATEX)
optional autotransformer regulator
remote start signal via potential free contact
remote thermocontact reset
EX PLUS features:
regulation through thermostat located in EX zone (ATEX)
START-STOP rotary switch
phase asymmetry, sequence, failure detection
overcurrent and short-circuit motor protection
thermistor motor protection relay MSR220VA (ATEX)
optional autotransformer regulator
remote start signal via potential free contact
remote thermocontact reset
weekly programmable start/stop signal
In case of motor overheat fan stops automatically and sends an overheat information to MSR220VA (KB1) module. To start
the heater user has to reset the module (additionally temperature of the fan needs to cool down). Fan motor has additional
overcurrent protection. Auxiliary protection is ensured by phase asymmetry, sequence, failure detection.