SOUND OUTPUT (SPL) SETTINGS:
Figure 2: Jumper plug settings for high, medium, low.
(Use needle nose pliers to pull and properly set the jumper
plugs)
WIRING INFORMATION:
FROM FACP PRECEDING
APPLIANCE OR SYNC
MODULE
When the sync module is used, the audible tone will be the code
3 sound only. Refer to Sync Module installation instruction
sheets SM (P83123), DSM (P83177) or PS-12/24-8 (P83862) for
additional information.
www.PDF-Zoo.com
Figure 1: Showing Location of Jumper Plug
CODE3
Factory setting is on medium dB and Code 3.
SHOWN SET ON HIGH dB
SHOWN SET ON MED dB
SHOWN SET ON LOW dB
NOTE: The AS must be set for code 3 when used with the sync module.
* Continuous horn operation without sync module.
Figure 4.
TO NEXT APPLIANCE OR
END-OF-LINE
RESISTOR (EOLR)
+
-
firealarmresources.com
HI
MED
LO
Figure 3: Jumper plug setting for Continuous Horn and
Code 3.
No jumper plug is needed for continuous horn setting.
However, it is recommended that the jumper plug be retained
in the unit for future use (if needed) as shown in Figure 3.
Figure 5.
1) AS Appliances have in-out wiring terminals
2) Break all in-out wire runs on supervised circuit
CODE 3
CONTIUOUS HORN *
TURN PLUG 90°
that accepts two #12 to 18 American Wire
Gauge (AWG) wires at each screw terminal.
Strip leads 3/8" inches for connection to screw
terminals.
supervision as shown in Figure 5. The polarity
as shown in the wiring diagrams is for the
operation of the appliances. The polarity is
reversed by the FACP during supervision.
P84024 D
Sheet 5 of 8