Flowmetrics PA-1001A Series Manual page 10

Signal conditioner & convertors

Advertisement

FOR CURRENT OUTPUT:
Connect a digital milliampmeter or equivalent, across the current output terminals.
On the PCA-121 select the "Coarse Range Adj" that corresponds to the maximum input
frequency. Refer to Table - 1 for selection options.
Adjust "4mA ADJ" control for desired "Zero" current (i.e. 4mA).
Inject the full-scale test frequency while adjusting "20mA ADJ" for current equal to SET (SPAN).
Iterate above steps until no change is observed.
FOR VOLTAGE OUTPUT:
NOTE: For proper adjustment of the voltage-output, First
Perform calibration of the current output.
Connect a digital voltmeter across the voltage output terminals.
On the PCA-121 select the "Coarse Range Adj" that corresponds to the maximum input
frequency. Refer to Table -1 for selection options.
Adjust "V
ADJ" for 0.00 volts).
O
Inject the test frequency while adjusting "V
Iterate above steps until no change is observed.
Control and Adjustment Detail for the PCA-121
PA1001A – 7/02
ADJ" for voltage equal to SET (SPAN).
FS
Page 10 of 11