OPERATING INSTRUCTIONS AND SPECIFICATIONS NI 9871 4-Port, RS485/RS422 Serial Module...
Page 2
This document describes how to use the National Instruments 9871 and includes specifications and pin assignments for the NI 9871. Visit and enter to determine ni.com/info rdsoftwareversion which software you need for the modules you are using. For information about installing, configuring, and programming the system, refer to the system documentation.
Touching this component may result in bodily injury. Safety Guidelines for Hazardous Locations The NI 9871 is suitable for use in Class I, Division 2, Groups A, B, C, D, T4 hazardous locations; Class I, Zone 2, AEx nA II T4 and Ex nA II T4 hazardous locations;...
Page 4
IP 54 as defined by IEC 60529 and EN 60529. For Zone 2 applications, install a protection Caution device between the RS232 signal cables and the NI 9871 RJ-50 jacks (ports 1–4). The device must prevent the RS232 signal-to-signal or signal-to-COM voltage from exceeding 35 V if there is a transient overvoltage condition.
Signal Name No Connect TXD– TXD+ RJ50 Jack RTS– TXD– CTS– TXD+ RTS– RXD– CTS– RXD– RXD+ RXD+ RTS+ CTS+ RTS+ CTS+ These signals are shared by all four RJ-50 connectors on the NI 9871. NI 9871 Operating Instructions ni.com...
Page 8
You must connect an external power supply to the NI 9871. This power supply provides the power for the RS485/RS422 transceivers on the module. You can use the included female four-position pigtail to connect to an external voltage source. Figure 1 lists the connections between an external voltage source (of +8 V to +28 V) and the NI 9871.
Page 10
Power Supply NI P/N 198159-XX: Female Microfit Pigtail Figure 2. Powering the NI 9871 from an Isolated Power Source Figure 3 shows how to use the optional y-adapter (available at ) to connect power to more than one module ni.com/serial using the same power source.
Maximum cable length ..... 1.2 km (4,000 ft.) Data line ESD protection (human body model)......±15 kV MTBF ..........514,016 hours at 25 °C; Bellcore Issue 6, Method 1, Case 3, Limited Part Stress Method NI 9871 Operating Instructions ni.com...
Page 16
Do not connect to signals or use for Caution measurements within Measurement Categories II, III, or IV. The maximum voltage that can be applied or output without creating a safety hazard. NI 9871 Operating Instructions ni.com...
Page 18
Operating temperature ...... –40 to 70 °C Storage temperature ......–40 to 85 °C Ingress protection......IP 30 Operating humidity......10 to 90% RH, noncondensing Storage humidity....... 5 to 95% RH, noncondensing NI 9871 Operating Instructions ni.com...
• ICES-001: Class A emissions For the standards applied to assess the EMC of this Note product, refer to the Online Product Certification section. For EMC compliance, operate this product Note according to the documentation. NI 9871 Operating Instructions ni.com...
Page 22
At the end of the product life cycle, all EU Customers products must be sent to a WEEE recycling center. For more information about WEEE recycling centers, National Instruments WEEE initiatives, and compliance with WEEE Directive 2002/96/EC on Waste and Electronic Equipment, visit ni.com/environment/weee...
Where to Go for Support The National Instruments Web site is your complete resource for technical support. At you have access to ni.com/support everything from troubleshooting and application development self-help resources to email and phone assistance from NI Application Engineers.
Page 24
LabVIEW, National Instruments, NI, ni.com, the National Instruments corporate logo, and the Eagle logo are trademarks of National Instruments Corporation. Refer to the Trademark Information at ni.com/trademarks for other National Instruments trademarks. Other product and company names mentioned herein are trademarks or trade names of their respective companies.