This document explains how to connect to the NI 9852. The NI 9852 module requires the latest NI 985x software to be installed. The latest version of the NI 985x software is at ni.com/ downloads. Before you begin, complete the software and...
Safety Guidelines for Hazardous Locations The NI 9852 is suitable for use in Class I, Division 2, Groups A, B, C, D, T4 hazardous locations; Class I, Zone 2, AEx nA IIC T4 and Ex nA IIC T4 hazardous locations; and nonhazardous locations only.
Special Conditions for Hazardous Locations Use in Europe and Internationally The NI 9852 has been evaluated as Ex nA IIC T4 Gc equipment under DEMKO Certificate No. 03 ATEX 0626664X and is IECEx UL 14.0089X certified. Each NI 9852 is marked...
Page 5
Wiring the NI 9852 The NI 9852 has two 9-pin male D-Sub connectors that provides connections to a CAN bus. Each port on the NI 9852 has pins for CAN_H and CAN_L, to which you connect the CAN bus signals.
Page 6
V pin on CAN0, and the V pin on CAN1. SUP0 SUP1 Pinouts for CAN0 and CAN1 of the NI 9852 are listed in Tables 1 and 2. 6 | ni.com | NI 9852 Getting Started Guide...
CAN_H SUP0 CAN Bus Topology and Termination A CAN bus consists of two or more CAN nodes cabled together. The CAN_H and CAN_L pins of each node are connected to the 8 | ni.com | NI 9852 Getting Started Guide...
Page 10
NI 9852 directly to one CAN node, and CAN1 directly to another CAN node. CAN0 and CAN1 require an external power supply on the CAN bus. Figure 2. Connecting Both Ports of the NI 9852 to CAN Buses (SHLD)
100 to 500 Ω (each) for a properly terminated low- speed network. Termination on the low-speed/fault-tolerant ports of the NI 9852 is set through the NI 985x software to either 1 kΩ or 5 kΩ. Number of CAN Nodes The maximum number of nodes depends on the electrical characteristics of the nodes on the network.
Page 13
The NI 9852 has two full-featured, independent CAN ports that are isolated from each other, and from the other modules in the system. Each port on the NI 9852 has a Philips SJA1000 controller that is CAN 2.0B-compatible and fully supports both 11-bit and 29-bit identifiers.
Page 14
Ext Pwr +5 V Supply 1 COM1 CAN_H CAN_L Transceiver Controller CAN1 NI 9852 Specifications The following specifications are typical for the range -40 °C to 70 °C unless otherwise noted. 14 | ni.com | NI 9852 Getting Started Guide...
Thermal dissipation (at 70 °C) Active mode 1.5 W max Sleep mode 1.2 W max Physical Characteristics To clean the module, wipe it with a dry towel. Weight Approx. 144 g (5.0 oz) 16 | ni.com | NI 9852 Getting Started Guide...
Page 18
Such voltage measurements include signal levels, special equipment, limited-energy parts of equipment, circuits powered by regulated low-voltage sources, and electronics. Do not connect the NI 9852 to signals or use Caution for measurements within Measurement Categories II, III, or IV.
EN 55011 (CISPR 11): Group 1, Class A emissions • AS/NZS CISPR 11: Group 1, Class A emissions • FCC 47 CFR Part 15B: Class A emissions • ICES-001: Class A emissions 20 | ni.com | NI 9852 Getting Started Guide...
Refer to the manual for the chassis you are using for more information about meeting these specifications. Operating temperature -40 °C to 70 °C (IEC 60068-2-1, IEC 60068-2-2) Storage temperature -40 °C to 85 °C (IEC 60068-2-1, IEC 60068-2-2) 22 | ni.com | NI 9852 Getting Started Guide...
China RoHS compliance, go to ni.com/environment/rohs_china Worldwide Support and Services The NI website is your complete resource for technical support. At ni.com/support, you have access to everything from 24 | ni.com | NI 9852 Getting Started Guide...