2.5 Assembling Leak Detection tape and connecting cables:
Tools required:
Crimping plier suitable for securing red pre-insulated terminals
(bullet connectors).
NB. If lengths of leak detection tape are being daisy chained
together with interconnection cable between each length of tape,
you will also require:
Red 0.5 - 1.5 mm² Insulated Male and Female Crimp Bullet
Connectors/Terminals with a copper sleeve and flared vinyl
insulation.
2 core audio cable.
Assembly
(see Figure 7)
1. To connect the 1.5M connection cable to a single length of leak
detection tape crimp the female bullet connectors at the end of
the connection cable into the male bullet connectors on the leak
detection tape.
Plug the connecting cable in to Input 'L' on the Water Valve
Control or the cable on the bottom of the Wireless Leak
Detection Transmitter.
2. To connect the 1.5M connection cable to two lengths of leak detection tape to make a longer length of tape, crimp the female
bullet connectors at the end of the cable into the male bullet connectors on the first length of leak detection tape, then crimp
the test pins of that tape in to the female bullet connectors on the next length of tape. A maximum length of 30M of tape can
be connected in this way.
Connect to the wireless Leak Detection Transmitter or Water Valve Control as detailed above.
3. To connect the 1.5M connection cable to two or more lengths of leak detection tape with interconnecting 2 core cable between,
crimp the female bullet connectors at the end of the 1.5M cable into the male bullet connectors on the first length of leak
detection tape. Cut the required length of 2 core cable and strip the insulating sheath off either end of the cable to expose the
wire. Crimp 2 male bullet connectors to the wires at one end and 2 female bullet connectors at the other, then crimp the test
pins on the first tape in to the female bullet connectors on the connecting cable and the male bullet connectors on the cable
into the female connectors on the next length of tape. A maximum of 30M of tape and interconnecting cable can be connected
in this way.
Connect to the wireless Leak Detection Transmitter or Water Valve Control as detailed above.
Figure 7.