Gentherm 5220 Operating Manual page 47

Thermoelectric generator
Hide thumbs Also See for 5220:
Table of Contents

Advertisement

7.2.2 V
After TEG has Stabilized
set
Once the TEG has been running for some time, typically more than an hour, the power
unit will be up to operating temperature.
Follow these steps to check V
a)
Consult the data plate inside TEG door for the reference V
mine the required V
or 7.1.2.
b)
Move the jumper clip on the terminal block TB-1 to the SETUP position, i.e.
between terminals 2 and 3. This connects the TEG to an internal load required
for V
set
c)
Connect a voltmeter between terminals 2 (+) and 4 (-). The measured V
should match the required V
Caution:
d)
Pause approximately 10-45 minutes and when the measured voltage is stable
compare it to required V
V
.
set
Note: Pausing is necessary to allow the TEG voltage to stabilize to the new load con-
ditions. (Changing from customer load to the on-board 1 ohm resistor).
Gentherm Global Power Technologies
5220
:
set
for the present ambient temperature. See Sections 7.1.1,
set
. See Figure 14 or 15.
Do not allow the measured V
will result and may cause irreparable damage to the power unit.
set
for the present temperature.
set
to exceed the required V
set
. Measured V
should be within 0.2 V of the required
set
28142 Rev. 14
voltage and deter-
set
, and
set
. Overheating
set
7-5