DISCOVER SOPzV Operating Manual

Gel tubular plate battery

Advertisement

Quick Links

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the SOPzV and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for DISCOVER SOPzV

  • Page 1: Table Of Contents

    Operating Manual TUBULAR GEL SOPzV 12V BLOCK 1. Safety 4.1 Charging 1.1 Do’s 4.1.1 Charge Parameters 1.2 Do Not’s 4.1.2 Balancing Charge 2. Delivery and Storage 4.1.3 Commissioning Charge 2.1 Receiving Inspection 4.2 Discharging 2.2 Storage 4.3 Temperature Limits 2.3 Unpacking and Handling 4.4 Charge Current Limits...
  • Page 2 • Analyzing and reducing hazards involved in performing electrical work • Installing and configuring batteries No responsibility is assumed by Discover for any consequences arising out of the use of this material. Visit discoverbattery.com for the most recent version of published documents.
  • Page 3: Safety

    Safety 1.1 Do’s • Do protect terminals from short circuit before, during, and after installation • Do wear electrically insulated gloves • Do use electrically insulated tools • Do wear eye protection • Do wear safety toe boots / shoes •...
  • Page 4: Unpacking And Handling

    (battery voltage and temperature) during service. 3.2 Batteries in Parallel Strings Discover Tubular Gel batteries may be connected in parallel to increase capacity, current capability and/or discharge durations. ®...
  • Page 5: Electrical Connections

    • The resistance of the cables or connector bars in each string must be the same, e.g. same cross-section, same length and same conductor type (copper, aluminum). • Each string should be equipped with disconnect capabilities (breakers) for maintenance and safety purposes. 3.4 Electrical Connections Battery cables must be sized to the specifications required by the inverter charger and must be installed in accordance with the standards set by the authority having local jurisdiction.
  • Page 6: Charge Parameters

    Nominal System DC Voltage Bulk & Absorption Charge Voltage 14.2V 28.4V 56.8V Current Limit 10A per 100Ah C10 rating Time Limitation Max. 6hrs Commissioning / Refresh charge settings (25°C/77°F) SELF-DISCHARGE CHARACTERISTICS SOPzV Blocks ˚C ˚C ˚C Storage Time (months) discoverbattery.com...
  • Page 7: Discharging

    -59°C / -74°F Discover Tubular Gel batteries can be stored in sub-freezing temperatures as low as -35°C / -31°F as long as they are fully charged prior to storage. The self-discharge rate of fully-charged batteries is very low in these conditions and they will not require charging for many months.
  • Page 8: Transport

    7. Recycling Discover’s lead acid batteries are recyclable products. All Discover Factory Warehouses and servicing dealers are qualified to accept and handle all used lead acid batteries. Contact Discover or your servicing dealer for details.
  • Page 9: Definitions & Abbreviations

    WHY DOESTHEVOLTAGE RISE VERY QUICKLY CAUSINGTHE CHARGERTO SHUT OFF WHEN I BEGINTO CHARGE MY BATTERY BANK? This is often an indication of sulphated batteries which can be confirmed by completing a load test • An increase in Absorption time may be necessary to sufficiently charge the battery to full SOC. WHY DOESTHE BATTERY BANK NOT REACHTHE BULK VOLTAGE SETTING WHEN CHARGING? If the system is not reaching the Bulk voltage, the charger voltage and/or Amp output to the battery bank may be too low.