6.15

Final checks

With the burner running
 Open the thermostat/pressure switch TL
 Open the thermostat/pressure switch TS
 Turn the gas maximum pressure switch knob to the mini-
mum end of scale position
 Turn the air pressure switch knob to the maximum end of
scale position
 Disconnect the minimum gas pressure switch connector
 Disconnect the maximum oil pressure switch connector
 Disconnect the minimum oil pressure switch connector
 Obscure the flame sensor
6.16

Pump motor lock-out

If the motor does not start, it could be because of a thermal relay
intervention due to its incorrect calibration or problems with the
motor or the main power supply, to release press the button of the
thermal relay, see "Calibration of the thermal relay" on page 21.
Start-up, calibration and operation of the burner
the burner must stop
the burner must stop in lockout
the burner must stop in lockout
the burner must stop in lockout
the burner must stop in lockout
the burner must stop in lockout due to flame loss