SYSTEM SPECIFICATIONS

System Capacity
• Intelligent Signalling Line Circuits....................................... 1
• Addressable device capacity .......................................... 198
• Programmable software zones ......................................... 99
• ACS Annunciators ............................................................ 32
• ANN-bus devices ................................................................ 8
Electrical Specifications
AC Power: MS-9200UDLS Rev 2: 120 VAC, 60 Hz, 3.0 amps.
MS-9200UDLS Rev 2E: 240 VAC, 50 Hz, 1.5 amps. Wire size:
minimum 14 AWG (2.00 mm²) with 600 V insulation.
Battery: Two 12 V 18AH lead-acid batteries.
Battery charger capacity: 7 – 18 AH. MS-9200UDLS Rev 2
cabinet holds maximum of two 18 AH batteries.
Communication Loop: Supervised and power-limited.
Notification Appliance Circuits: Each terminal block pro-
vides connections for two Style Y (Class B) or one Style Z
(Class A) for a total of four Style Y (Class B) or two Style Z
(Class A) NACs. Maximum signaling current per circuit: 2.5
amps. End-of-Line Resistor: 4.7K ohm, 1/2 watt (P/N 71252
UL listed) for Style Y (Class B) NAC. Refer to panel documen-
tation and Fire•Lite Device Compatibility Document for listed
compatible devices.
Two Programmable Relays and One Fixed Trouble Relay:
Contact rating: 2.0 amps @ 30 VDC (resistive), 0.5 amps @ 30
VAC (resistive). Form-C relays.
Special Application Power (24 VDC Nominal): Jumper
selectable (JP4) for conversion to resettable power output. Up
to 0.3 amps total DC current available from each output.
Power-limited.
Four-Wire Resettable Special Application Smoke Detector
Power (24 VDC nominal): Up to 0.3 amps for powering four-
wire smoke detectors. Power-limited. Refer to the Fire•Lite
Device Compatibility Document for listed compatible devices.
Remote Sync Output: Remote power supply synchronization
output. Nominal special application power: 24 VDC. Maximum
current: 40 mA. End-of-Line Resistor: 4.7K ohm. Output linked
to NAC 1 control. Supervised and power-limited.
Telephone Interface: Unless used with Teldat VISORALARM,
requires dedicated business telephone number with a mini-
mum of 5 volts DC (off-hook voltage). Obtain dedicated phone
line directly from your local phone company. Do not use shared
phone lines or PBX (digital) type phone line extensions.
Cabinet Specifications
Door: 19.26" (48.92 cm.) high x 16.82" (42.73 cm.) wide x
0.12" (.30 cm.) deep. Backbox: 19.00" (48.26 cm.) high x
For more information, contact Fire•Lite Alarms. Phone: (800) 627-3473, FAX: (877) 699-4105.
Page 6 of 6 — DF-60415:C • 12/17/2009
This document is not intended to be used for installation purposes.
We try to keep our product information up-to-date and accurate.
We cannot cover all specific applications or anticipate all requirements.
All specifications are subject to change without notice.
www.firelite.com
16.65" (42.29 cm.) wide x 5.20" (13.34 cm.) deep. Trim Ring
(TR-CE): 22.00" (55.88 cm.) high x 19.65" (49.91 cm.) wide.
Shipping Specifications
Weight: 26.9 lbs. (12.20 kg.) Dimensions: 20.00" (50.80 cm.)
high x 22.5" (57.15 cm.) wide x 8.5" (21.59 cm.) deep.
Temperature and Humidity Ranges
This system meets NFPA requirements for operation at 0 –
49°C/32 – 120°F and at a relative humidity 93% ± 2% RH
(noncondensing) at 32°C ± 2°C (90°F ± 3°F). However, the
useful life of the system's standby batteries and the electronic
components may be adversely affected by extreme tempera-
ture ranges and humidity. Therefore, it is recommended that
this system and its peripherals be installed in an environment
with a normal room temperature of 15 – 27°C/60 – 80°F.
NFPA Standards
The MS-9200UDLS Rev 2 complies with the following NFPA
72 Fire Alarm Systems requirements:
– LOCAL (Automatic, Manual, Waterflow and Sprinkler
Supervisory).
– AUXILIARY (Automatic, Manual and Waterflow) (requires
4XTMF).
– REMOTE STATION (Automatic, Manual, Waterflow and
Sprinkler Supervisory) (Where a DACT is not accepted,
the alarm, trouble and supervisory relays may be con-
nected to UL 864 listed transmitters. For reverse polarity
signaling of alarm and trouble, 4XTMF is required.)
– PROPRIETARY (Automatic, Manual, Waterflow and
Sprinkler Supervisory).
– CENTRAL STATION (Automatic, Manual, Waterflow and
Sprinkler Supervisory).
– OT, PSDN (Other Technologies, Packet-switched Data
Network)
Agency Listings and Approvals
The listings and approvals below apply to the basic MS-
9200UDLS Rev 2 control panel. In some cases, certain mod-
ules may not be listed by certain approval agencies, or listing
may be in process. Consult factory for latest listing status.
• UL: S624
• FM approved
• CSFM: 7165-0075:208
• MEA: 120-06-E
LiteSpeed™ is a trademark; and FireLite® Alarms is a registered trademark
of Honeywell International Inc. Microsoft® and Windows® are registered
trademarks of the Microsoft Corporation.
©2009 by Honeywell International Inc. All rights reserved. Unauthorized use
of this document is strictly prohibited.
Made in the U.S. A.

Advertisement

loading

This manual is also suitable for:

Fire-lite alarms ms-9200udlse