Interlogix SuperBus 2000 Installation Instructions page 4

2-amp power supply

Advertisement

3.
Wire the power supply AC transformer to the power supply
board, then plug in the transformer
LED should turn on to indicate power is present. The red
LED should be off for the moment.
Note: If the green LED is not on, unplug the power supply
AC power transformer, disconnect the backup battery, and
proceed to
Table 2
in "Troubleshooting".
4.
Connect the panel backup battery and plug in the panel
AC power transformer. The panel should automatically
scan for new bus devices and the red LED on the power
supply board should flicker to indicate bus communication
with the panel.
5.
If using the optional zone input, learn the zone into panel
memory (see panel installation instructions).
Troubleshooting
Table 2. Troubleshooting
Problem
Action
Green LED is off
1. Check that power supply transformer is
plugged into outlet.
2. Check that transformer is not plugged into
an outlet controlled by a switch.
3. Check outlet circuit breaker/fuse. Reset/
replace as needed.
Red LED is off.
Check/correct bus (A & B) wiring connections
at module and panel.
System touchpads
1. Check for shorts on wire connected to
display AUX POWER
power supply +12V OUT terminal.
FAIL.
2. Verify that devices connected to power
supply +12V OUT terminal are not drawing
more than 2 amps.
System touchpads
1. Check that power supply battery is
display AUX POWER
connected.
BATT trouble.
2. Power supply battery needs charging.
Battery may need at least 4 hours to fully
charge.
System touchpads
1. Check that power supply transformer is
display AUX AC
plugged into outlet.
POWER trouble.
2. Check that power supply transformer is not
plugged into an outlet controlled by a switch.
3. Check outlet circuit breaker/fuse. Reset/
replace as needed.
4
(Figure
10). The green
Specifications
Panel compatibility
Concord 4 series control panels
Power output required
24 VAC, 50 VA class II power transformer
Power output
12 VDC, 2.0 amps maximum, current limited
Battery type
12V, 4.5Ah or 7Ah lead acid
Standby load
95 mA (4.5Ah battery), 190 mA (7 Ah battery)
Operating temperature
32° to 120° F (0° to 49° C)
Storage temperature
-30° to 140° F (-34° to 60° C)
Max. relative humidity
85%, non-condensing
Dimensions (LxWxD)
5.125 in. x 7.85 in. x 1.0 in. (13 cm x 20 cm x
2.5 cm)
Regulatory information
Manufacturer
UTC Fire & Security Americas Corporation, Inc.
1275 Red Fox Rd., Arden Hills, MN 55112-6943,
USA
UL/cUL listings
985, 1023, and 1610
FCC compliance
This device complies with FCC Rules Part 15.
Operation is subject to the following two
conditions. This device may not cause harmful
interference. This device must accept any
interference that may be received, including
interference that may cause undesired operation.
Changes or modifications not expressly approved
by Interlogix can void the user's authority to
operate the equipment.
Contact information
For contact information, see www.utcfireandsecurity.com or
www.interlogix.com.
For technical support, toll-free: 888.437.3287 in the US
including Alaska, Hawaii, Puerto Rico, and Canada. Outside
the tool-free area, contact your dealer.
Copyright © 2011 Interlogix, a UTC Fire & Security Company.
All rights reserved.
SuperBus 2000 2-Amp Power Supply 600-1019 Installation Instructions