3. Receiving, handling and storage

VM1/A/P circuit breakers are subject to complete
factory production tests and inspection prior to
packaging and shipment. The shipping package is
designed to provide reasonable protection during
shipment and to provide convenient handling.
Accessories such as opening handles and racking
handles are shipped separately from the circuit
breaker.
The circuit breaker is shipped in special packing, in
the open position.
Each piece of apparatus is protected by a plastic
cover to prevent any infiltration of water during the
loading and unloading stages and to keep the dust
off during storage.
3.1. Receiving and checking
On receipt, check the state of the apparatus,
integrity of the packing and correspondence with
the nameplate data (see Fig.1) with what is
specified in the order confirmation and in the
accompanying shipping notes.
Also make sure that all the materials described in
the shipping notes are included in the supply.
Should any damage or irregularity be noted in the
supply on unpacking, notify ABB (directly or
through the agent or supplier) as soon as possible
and in any case within five days of receipt.
The apparatus is only supplied with the accessories
specified at the time of ordering and validated in
the order confirmation sent by ABB.
Before carrying out any operation, always
make sure that the capacitors are
discharged and that the apparatus is in the
open position.
The accompanying documents inserted in the
shipping packing are:
• instruction manual (this document)
• test certification
• identification label
• copy of the shipping documents
• electric wiring diagram.
Other documents which are sent prior to shipment
of the apparatus are:
• order confirmation
• original shipping advice notes
• any drawings or documents referring to special
configurations/conditions.
CIRCUIT-BREAKER
A
VM1/A/P 15.12.32
C LASSIFICATION
3
1VC1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SN
MASS
VOLTAGE
LIGHTNING IMPULSE WITHSTAND VOLTAGE
FREQUENCY
NORMAL CURRENT
SHORT TIME WITHSTAND CURRENT
DURATION OF SHORT CIRCUIT
4
SHORT CIRCUIT BREAKING CURRENT
D.C. COMPONENT
RATED INTERRUPTING TIME
INSTRUCTION BOOK
CABLE-CHARGING BREAKING CURRENT
OPERATING SEQUENCE
ELECTRICAL DIAGRAM 1VCD400051 (E0926)
FIG.01 FIG.02 FIG.05 FIG.OS FIG.12
ll l llll l IIl l ll l llIllll l llI l llll l lll l ll l ll l llI l Illlll l lIlll l lllI l lllll l ll l
B
A3
-RL2
AUXILIARY VOLTAGE
5
Made by ABB, Italy
Caption
A
Circuit breaker rating plate.
B
Drive rating plate.
1
Type of apparatus.
2
Symbols of compliance with Standards.
3
Serial number.
4
Circuit breaker characteristics.
5
Characteristics of the drive auxiliaries.
Fig. 1
7 7
1
2
ANSI C37.04
PR. YEAR 2010
84
kg
15
kV
95
kV
60
Hz
1200
A
31.5
kA
2
s
31.5
kA
< = 40
%
< = 50
ms
1VCD600916R000
A
O-0,3S-CO-3MI N-CO
OPERATING MECHANISM
110 V
110...250 V
100...240 V