Siemens SIKOSTART 3RW35 Instruction Manual page 24

Hide thumbs Also See for SIKOSTART 3RW35:
Table of Contents

Advertisement

S
olid State Outputs
Seven are available for the user
Electrical Data
Operational Current
Catalog
Rating
Number
(Amperes)
3RW3552...
35
3RW3554...
57
3RW3555...
69
3RW3557 ...
80
3RW3558...
105
3RW3565...
131
3RW3566...
195
3RW3567 ...
248
3RW3572...
361
3RW3583...
480
3RW3584...
720
3RW3586...
960
* Fuse rating should not exceed 175% of full load motor rating for class RK1 and L fuses for Type 2 protection.
Controller
Current Rating
(Amperes)
Control
35, 57
69, 80, 105
131, 195, 248
361
480, 720, 960
24
Rating
Run #1 & 2 Instant
Contact NO
Run #1 & 2 Delayed
Contact NO
Fault NO & NC
Up - To - Voltage
Power Dissipation
@ Rated Current
(Watts)
84
154
166
192
252
315
468
595
866
1152
1728
2304
Current Required
(Milliamperes)
120V AC Control Voltage
Fans
100
N/A
100
200
100
150
100
300
100
450
NO & NC contacts are rated at 1.0 Amp at 120V AC.
When controller is operating, the RUN contact is closed.
NO contact closes immediately on RUN, but delays 100ms
on dropout.
The FAULT NO contact closes and FAULT NC contact opens
for a shorted thyristor.
When NO contact closes, motor is running at 95% to 100%
of line voltage (after starting is completed).
Surge Capacity
I
2
t, (1/2 cycle)
(1 cycle)
Controller
(Amps)
(A
2000
15,000
2,250
18,000
4,000
80,000
4,000
80,000
7 ,850
257 ,000
7 ,850
257 ,000
7 ,850
234,000
11,000
416,000
15,000
815,000
29,000
2,600,000
29,000
2,600,000
61,000
15,800,000
Siemens Energy & Automation, Inc.
Current Limit
Dual Element
2
-sec)
Fuse Rating*
60A - RK1
100A - RK1
100A - RK1
100A - RK1
150A - RK1
200A - RK1
300A - RK1
400A - RK1
600A - RK1
800A - RK1
1200A - RK1
1600A - RK1