Lindab WH45P Technical Manual page 6

Hide thumbs Also See for WH45P:
Table of Contents

Advertisement

WH45P
WH45P
ovER vIEW
EI 90 S Installation within floor  p. 23
Floor minimum thickness 100 mm
Floor minimum density 650 kg/m³
Mortar sealing
ho (i↔o)
EI 120 S Installation within floor  p. 23
Floor minimum thickness 150 mm
Floor minimum density 650 kg/m³
Mortar sealing
ho (i↔o)
EI 180 S Installation within floor  p. 23
Floor minimum thickness 150 mm
Floor minimum density 2200 kg/m³
Mortar sealing
ho (i↔o)
Ø is the minimum and maximum nominal diameter of fire dampers in mm
ve
Vertical installation
ho
Horizontal installation
(i↔o) Origin of fire irrelevant
Pa
Pascal of depression
E
Integrity
I
Thermal insulation
S
Smoke seal
W
Wet method sealing
D
Dry method sealing
Cert. N° 1812-CPR-1107
1.8.1.
Fire Batt (Weichschott) sealings
EI 120 S Installation within vertical rigid wall with Fire Batt (Weichschott) sealing  p. 24
Wall minimum thickness 100 mm
Wall rock wool minimum density 500 kg/m³
Rock wool 140 kg/m³ and endothermic varnish sealing
ve (i↔o)
Minimum distance allowed between 2 dampers
EI 120 S Installation within vertical light wall (plasterboard) with Fire Batt (Weichschott) sealing  p. 24
Wall minimum thickness 100 mm
Wall rock wool density up to 100 kg/m³ (optional)
Rock wool density 140 kg/m³ and endothermic varnish sealing
ve (i↔o)
Minimum distance allowed between 2 dampers
EI 120 S Installation within vertical light wall (gypsum blocks wall) with Fire Batt (Weichschott) sealing  p. 24
Wall minimum thickness 100 mm
Wall minimum density 995 kg/m³
Rock wool 140 kg/m³ and endothermic varnish sealing
ve (i↔o)
Minimum distance allowed between 2 dampers
EI 90 S Installation within floor and Fire Batt (Weichschott) sealing  p. 25
Floor minimum thickness 150 mm
Floor minimum density 650 kg/m³
Rock wool 140 kg/m³ and endothermic varnish sealing
ho (i↔o)
Minimum distance allowed between 2 dampers
Ø is the minimum and maximum nominal diameter of fire dampers in mm
ve
Vertical installation
ho
Horizontal installation
(i↔o) Origin of fire irrelevant
Pa
Pascal of depression
E
Integrity
I
Thermal insulation
S
Smoke seal
W
Wet method sealing
D
Dry method sealing
Cert. N° 1812-CPR-1107
6
6/42
EI 180 S
(500 Pa)
W
-
W
-
Ø
W
min 200
max 800
EI 120 S
(300 Pa)
Ø
W
min 200
max 800
200 mm
Ø
W
min 200
max 800
200 mm
Ø
W
min 200
max 800
200 mm
W
-
-
We reserve the right to make changes without prior notice
rev 20-10
EI 120 S
EI 90 S
EI 60 S
(500 Pa)
(500 Pa)
(500 Pa)
Ø
-
min 200
min 200
max 800
max 800
Ø
Ø
min 200
min 200
min 200
max 800
max 800
max 800
Ø
Ø
min 200
min 200
min 200
max 800
max 800
max 800
EI 90 S
EI 60 S
(300 Pa)
(300 Pa)
Ø
Ø
min 200
min 200
max 800
max 800
50 mm
50 mm
Ø
Ø
min 200
min 200
max 800
max 800
50 mm
50 mm
Ø
Ø
min 200
min 200
max 800
max 800
50 mm
50 mm
Ø
Ø
min 200
min 200
max 800
max 800
200 mm
200 mm
EI 30 S
(500 Pa)
Ø
Ø
min 200
max 800
Ø
Ø
min 200
max 800
Ø
Ø
min 200
max 800
EI 30 S
(300 Pa)
Ø
min 200
max 800
50 mm
Ø
min 200
max 800
50 mm
Ø
min 200
max 800
50 mm
Ø
min 200
max 800
200 mm