Opening/Closing the Luminaire
This luminaire has 2 lids, a driver enclosure lid
and front access lid. Both lids are retained by
captive bolts and offer a combination head
style for ease of entry. The front access lid is
used for wiring the luminaire for bracket
models while slip fitter models do not use the
front access lid.
Loosen the 4x screws and remove the lid to
gain access to the terminal blocks for wiring.
When wiring is complete, reattach the lid,
and tighten screws back down.
Torque: 3,4 N-m [30 in-lbs]
4x Captive Bolts
NOTE: The lid is secured to the wiring box via
a lanyard; eliminating risk of dropping the lid
upon removal.
NOTE: The lid of the luminaire should be
oriented as shown above. The Dialight logo
should be aligned with the mounting bracket.
Electrical Connections
The terminal block is suitable for multi-
stranded or single core wires. The parameters
can be found in Technical Data.
Push Down Terminal Models: F*B********V**
Push down at the 'cross point', insert wire, and
release.
Conductor Range
0,5-4 mm² [20-12 AWG]
Screw Down Terminal Models: F*B********U**
For input power terminal block, loosen
terminal screw, insert wire, and tighten screw.
Conductor Range
0,5-6 mm² [20-10 AWG]
10 mm [0,39 in.]
9100FLM000903 REV B
Page 4 of 20
ProSite Floodlight for ATEX/IECEx Zone 2
For dimming & Dali lines, push down at the
'cross point', insert wire, and release.
Conductor Range
0,5-4 mm² [20-12 AWG]
Single Phase Connections
The connections are marked on the terminal
block or on a label and are presented in the
table below.
SYMBOL
N
L
N
L
DIM +
DIM -
DALI
0-10 VDC Dimming (If Applicable)
Dimming is controlled by means of a 0-10
VDC signal (to be provided by the installer) to
control the level of dimming. At 10 volts, the
output of the unit is 100%; at 0 volts, the output
will shut off. The DC dimming voltage should
not exceed 15 VDC. Increasing the voltage
from 10 VDC to 15 VDC will not result in
additional light output.
WARNING: Never connect the dimming wires
to the Hot or Neutral supply wires.
An analog 0-10 V active dimmer may be
connected to the two wires to control the
light output of the fixture. Multiple lights may
be connected to the same dimmer, as long
as the maximum current rating of the dimmer
is not exceeded.
See table for current sinking capabilities of
the
dimmer.
approximately linearly with control voltage,
with 10 V corresponding to 100% light output.
Strip Length
9 mm [0,35 in.]
F1B***********
F2B****(F/H)******
F2B****(L/N)******
Strip Length
Strip Length
9 mm [0,35 in.]
COLOR
CONNECTION
120-277VAC
GREEN/
EARTH/
YELLOW
GROUND
WHITE
NEUTRAL
BLACK
LIVE
130-250VDC
GREEN/
EARTH/
YELLOW
GROUND
WHITE
BLACK
+
CONTROLS
VIOLET
DIMMING +
GREY
DIMMING -
ORANGE
DALI
OR YELLOW
Variable Voltage Control
Light
output
will
Part Number
Current
0,5 mA
0,5 mA
1,0 mA
Dialight, 1501 Route 34 South, Farmingdale, NJ, USA 07727
Tel: +1 732 919 3119 Fax: +1 732 751 5778
NOTE: Simply shorting the two wires together
will cause the light to shut off.
WARNING: Improper installation, operation,
or maintenance of this luminaire may result in
the invalidation of the warranty, certificate,
or declaration of conformity.
DALI Control (If Applicable)
DALI is used to control/schedule and group
the luminaire. A DALI controller is to be
provided by the installer. The luminaire will not
provide a bus signal. A Bus power supply
should be used to provide a Bus signal
-
according to the DALI standard.
WARNING: Never connect the DALI wires to
the Hot/Live or Neutral supply wires.
WARNING: Do not connect the DALI wires to
the dimming wires.
For luminaires containing one power supply
[F1B********** & F2B****(F/H)******], only one
DALI address will be assigned by the DALI
controller.
For luminaires containing two power supplies
[F2B****(L/N)******], two DALI addresses will
be assigned by the DALI controller.
NOTE: The DALI circuit in two power supply
luminaires are already internally wired as a
daisy chain to allow for commissioning and
discovery. The
connected to the DALI terminal block
positions in the wiring compartment.
vary
NOTE: Make sure luminaires containing two
power supplies are grouped and scheduled
together for the luminaire to function in the
correct manner.
WARNING: Improper installation, operation,
or maintenance of this luminaire may result in
the invalidation of the warranty, certificate,
or declaration of conformity.
Bus wire
needs to be