Reset Button
The system can be reset by pressing the reset button located on the front panel.
Alarm/Status LEDs
LED
State
Critical
Off
Red
Major
Off
Red
Minor
Off
Red
Status
Off
Green
Green Flashing
Green/Yellow
Yellow
Yellow Flashing
Red
Adit 3104 - Release 1.6
Description
No critical alarms present
Critical alarms present. Critical alarms include:
user-configured manor environmental inputs.
No major alarms present
Major alarm present. Major alarms include:
user-configured manor environmental inputs, DS1 short, DS1 open, DS1
facility alarm, DS1 RAI, DS1 AIS, DS1 LOF, DS1 LOS, WAN fault,
Ethernet fault and dead card alarms.
No minor alarms present
Minor alarms present. Minor alarms include:
user-configured minor environmental inputs, DS1 excessive line code
violations.
No power to system
Application running, no detected system problems.
Power-On Self Test (POST) successful. System booted. Loading
Application.
Flashing alternate colors. Application Self Test in Process.
Yellow while booting. If this stays a steady yellow the Power-On Self Test
(POST) failed.
Power-On Self Test (POST) In Process.
System Failure
Electrical Installation & Cabling
Reset Button
3-9