Event Message
-48V DC power A/B
Low or Missing
Alarm Input 1/2/3
Detected
Controller A/B
Incompatible
Controller A/B Removed Upon removal the controller card
Controller A/B software
version mismatch
DS1 n Major Line CV
Access Navigator - Release 1.8
Table 14-3 CLI Minor Alarm Message and Trouble Clearing Procedure
Description
-48V DC power supply to the
controller (A or B) is low or
missing. Under normal condition
power is shared between controller
cards.
Contact closure was detected on
the indicated alarm input (1,2, or
3). Alarm inputs can be wired to
the facility alarm system. Under
normal conditions the facility
alarm system should provide open
contacts to the alarm inputs.
Providing contact closure to an
alarm input results in this alarm.
Controllers do not support the
same functionality; for example,
one supports EOC/TMC and the
other does not.
(A or B), the remaining controller
card is now active.
Controller card software versions
do not match.
DS1 is receiving Line Code
Violations at a rate greater than
1.0 x 10-3. This indicates a weak
signal or faulty wiring.
August 2003
Alarm Clearing
Clear Alarms – FDL
Trouble Clearing Procedure
Check power cable connection or
battery voltage of the reporting
controller card.
The alarm is cleared when the
contact is opened.
Remove the standby controller and
replace with a compatible
controller (see Replace Controller
Card on
page 16-3
or update
controller with compatible
software (see Update Controller
Card Software on
page
Insert a good controller card into
the empty slot
Update offending controller with
appropriate software (see Update
Controller Card Software on
page
17-1).
Correct the problem with the
incoming DS1 signal, or use
following command to provision
the DS1 as out of service:
set ds1 <n> <up|down>
17-1).
14-5