The 13406 Remote LED Annunciator Driver Board is an optional module for the 13400 Fire Alarm System
Control Unit. The 13400 control unit provides an optional drive for a remote annunciator. While the
remote interface is via individual drive circuits, the physical connection between the control unit and the
annunciator uses parallel data and draws all power from the control unit. The control unit will supervise 1
remote unit. Annunciator wiring is supervised for open conditions. The board mounts to the Main Board
of the 13400 Fire Alarm System Control Unit.
PARTS SUPPLIED
1
13406
Remote LED Annunciator Driver Board
4
942456
Spacer, 5/8"
1
446694
Instruction Sheet
13406 WIRING
Power Limited
Supervised
For opens only
NOTES:
1.)
Units to be installed in accordance with all local
electrical codes.
2.)
Terminal block will accept a maximum of #12
AWG wiring.
446694 ISSUE I
INSTALLATION INSTRUCTIONS AND WIRING FOR
REMOTE LED ANNUNCIATOR DRIVER BOARD
Cat. No. ADB Part No. 13406
7704 / 7704-01
Annunciator
firealarmresources.com
Step 1.) Installation is to be done by qualified personnel
who have thoroughly read and understood this
instruction sheet.
Step 2.) Disconnect all power into system, including
batteries.
Step 3.) Attach conduit and run wires as required.
Step 4.) Mount Remote LED Anuunciator Driver Board as
shown, using four spacers (P/N 942456) to Main
Board.
Step 5.) Connect wires to fire alarm system control unit as
required.
Step 6.) Apply power to system.
Step 7.) Check for proper operation of functions.
Not
Supervised
13406 MOUNTING
Spacers
J1 connector mates with
J1 on Main Board