Appendix A : Reference Data
This appendix provides reference for the following topics:
•
Wire selection guides
•
Battery size calculations
Wire Selection Guides
Resistance of Solid Copper Wire
AWG
18
16
14
12
+
N.E.C. Chapter 9, Table 8.
Initiating Device Circuit Wire Selection Guide
Each initiating circuit loop must not have a resistance greater than 100 ohms. The
following chart is based on the resistance of solid copper wire.
Maximum Wire Loop Distance (feet)
18 AWG
12,376
Notification Appliance Circuit Wire Selection Guide
Each Notification Appliance Circuit loop must not have a voltage drop greater than 1
volt. The following chart is based on the following premises:
1. All of the load is at the end of the wire run (worst case).
2. Resistance is of solid copper wire
Contact your local distributor or the factory if further information is needed in your
circumstances.
Maximum Wire Loop Distance (Feet)
Signal
Load
(A.)
P/N 446613 Issue I Rev. A
+
Ohms per
Thousand Feet
8.08
5.08
3.19
2.01
16 AWG
14 AWG
19,685
31,347
18 AWG
16 AWG
0.1
1,237
0.25
495
0.5
247
0.75
165
1.0
123
1.25
99
1.5
82
firealarmresources.com
13400 Owner's Manual
12 AWG
49,751
14 AWG
12 AWG
1968
3134
787
1253
393
626
262
417
196
313
157
250
131
208
4975
1990
995
663
497
398
331
A-1