Gemo DT109AX Installation & Use page 3

Auto-tune pid temperature controller

Advertisement

GEMO
Press for 2 sec.
CodE
SET
Back
Press "Back"
to return to the
SET
top of
parameters
programming
block
SET
H.hys /
SET
AL.tY
SnS.O
A.hys
or
SET
SnS.F
SET
SET
H.Hys
not 0
SET
SET
SET
SET
SET
SET
AL.tY=
Abs,-Abs,
SnS.O,
SET
SnS.F
h-C=
C.dLY
heat
SET
SET
SET
L.dSP
SET
H.Hys
not 0
SET
SECU
SET
End Prog.
(1) When sensor type is changed, Up.L, Lo.L, H.Set, A.Set, H.hys,
A.hys, r.Alr, b.Alr, oFFs may be set to a new value automatically,
according to the selected sensor.
(2) ON-OFF control is the only option for Cooling function
(3) If sensor type is selected as Pt.0, J.0, K.0 or t.0.
Gürbüzoğlu Elektronik San. ve Tic. Ltd. Şti.
Çamlıtepe Cad. No:297 / 3-4 Siteler, Ankara, Türkiye
Tel: +90-312-3503900, Fax: +90-312-3511117
PROGRAMMING PARAMETERS
+
SET
Upper Display
Enter 162
Inpt
Sensor Type (1)
Select
h-C
function (2)
0 .. 50 /
0.0 .. 50.0 (3)
C.hys
o
C
1 .. 50 /
0.1 .. 50.0 (3)
o
C
Pb.C
5 .. 150
o
C
Ct
1 .. 200 sec
0:00 .. 30:00
ti
min:sec
0:00 .. 10:00
td
min:sec
Lo.L ..
UP.L
Upper Scale (
o
C)
Lower Scale ..
Lo.L
UP.L (
o
C)
-100 .. 100 /
oFFS
-100.0 .. 100.0 (3)
O
C
Abs,rel,bnd,bn.i
-Abs,-rel,
AL.tY
-bnd,-bn.i,
SnS.O, SnS.F
-100 .. 100 /
r.ALr/
-100.0 .. 100.0 (3)
b.ALr
O
C
0 .. 300 sec
P.Err
% 0 .. 100
0.0 .. 300.0
C-t
o
C / min
yes .. no
OFF, 10.0,
o.Sht
5.0, 3.0,
1.0, 0.2
AH, -H, A-, --
Enter 162 to pass
to parameter prog. mode
J, J.0: J type T/C
K, K.0: K type T/C
t, t.0: T type T/C
S: S type T/C
SET
r: R type T/C
Pt, Pt.0: Pt100
HeAt: heating function
• Before starting Auto-tune, adjust H.SET.
Cool: cooling function
• Auto-tune does not start in "cooling" mode.
• Process value may exceed H.Set during auto-tuning.
Heat/Cool Hysteresis (
o
C):
• After auto-tuning, control form automatically switches
PID is active if set to 0
to PID mode.
• Auto-tuning is stopped (interrupted) any time by
(for H.Hys) (
o
C)
pressing any key. In this case, the parameters before
auto-tuning is valid.
• Auto-tuning may not always determine the best values
Alarm Hysteresis (
o
C)
for your process.
Proportional Band in (
C)
o
SET
Control period (sec)
"YES" / "nO"
Integral Time:
• To return to factory settings:
In min:sec If set to 0:00,
Code > 555 > select "yes" >
P, PD is active (integral OFF).
Press "SET"
Derivative Time:
In min:sec. If set to 0:00,
P, PI is active (derivative OFF).
Upper limit value for Lo.L,
H.SET and A.SET. Upper Scale value
differs according to the selected
sensor type.
Lower limit value for UP.L,
H.SET and A.SET. Lower Scale value
differs according to the selected
sensor type.
Offset Value; Offset is directly added
to the measured value. This feature shall
be used for user calibration. Normally set to 0.
Alarm Type:
Abs: Absolute
-Abs: Absoloute, invert out SnS.O: Sensor failure
rel: Relative
-rel: Relative, invert out
bnd: band
-bnd: band, invert out
bn.i: band inhibit
-bn.i: band, invert out
Relative or band Alarm
Value. Displayed if AL.ty is
other then Abs or –Abs.
Active only in cooling mode.
Minimum delay before OUT
becomes ON after it becomes OFF.
Determines the duty cycle of OUT output
when "Fail" message is displayed. If 0, OUT is always
OFF. If 100, OUT is always ON, when device "fails".
Period is Ct.
If C-t is not 0, ramping starts after power on. SET value
is incremented or decremented C-t degrees per minute
until SET reaches H.SEt or C.SEt.
yes: Lower display ON
no: Lower display OFF
Over shoot reduction: All options other than "OFF" may help to reduce over
shoot more but also may increase instability around SET point. For this reason;
First try "OFF" option then 10.0->5.0->3.0->1.0->0.2 options if needed.
Options 1.0 and 0.2 are most sensitive and may result more instability around
SET point among other options. With this parameter, over shoot is not allowed
more than; OFF: not limited, 10.0: 10 , 5.0: 5 , 3.0: 3 , 1.0: 1 , 0.2: 0.2 degrees
(over SET point).
AH: ALARM SET and HEAT SET may be SET,
-H : Only HEAT SET may be SET,
-A : Only ALARM SET may be SET,
-- : ALARM SET and HEAT SET may not be SET.
Error Messages:
Fail: Sensor failure or sensor selection wrong
E.FLS: Hardware failure
E.CAL: Hardware failure
E.EPr: Memory failure
3
Upper Display
Enter "262"
to start
CodE
auto-tune
"tunE"
flashes
Upper Display
Factory SET Values:
H.SEt: 100
Enter "555"
CodE
A.SEt: 400
for factory
Inpt : J
reset
H-C : Heat
H.hys: 0
A.hys: 3
Pb.C: 30
Ct: 4 sec
ti: 5:00 min:sec
td: 1:00 min:sec
UP.L: 400
Lo.L: 0
oFFS: 0
AL.tY : rel
r.ALr: 3
C.dLY: 15 sec
P.Err: 0
C-t: 0.0
L.dSP: yes
o.Sht: oFF
SECU: AH
Continuous out
SnS.F: Sensor failure
Flashing out
http://www.gemo.com.tr.