Download Print this page

Gemo DT109AX Installation & Use page 2

Auto-tune pid temperature controller

Advertisement

GEMO
This device and its packing is NOT litter and may NOT be disposed of with domestic waste. Please return
this device and its packing to an appropriate recycling point at the end of its service life.
Please read this user manual carefully and completely before installation and use. Please take into
consideration all warnings mentioned in this manual.
DT109AX,DT107AX,DT106AX,DT105AX,DT104AX
Installation and use of this device must be done by qualified, authorized and trained technical personnel only.
Inspect device carefully before installation. Do not install and use broken and defective devices.
Do not disassemble device. Do not make any repair on any part of the device. There is no accessible part
inside the device. Please contact to manufacturer for broken and defective devices.
Do not use device in environments subject to flammable, explosive and corrosive gases and/or substances.
This device is designed for applications only in light industrial environments. This device is not suitable for
medical and residential use. This device is not suitable for use related with human health and safety. This
device is not suitable for automotive, military and marine use.
Do not allow children and unauthorized people to use this device.
Before installation and any technical work, disconnect the power supply and mains connections.
Check the power supply voltage level before power on, and make sure voltage level is in specified limits.
Check quality of neutral line. Improper neutral line may give permanent damage to the device.
Connect an external power switch and an external fuse (1A, 250VAC) to the power supply line that are easily
accessible for rapid intervention. Connect an external fuse (2A, 250VAC) for each relay output separately.
Use appropriate cables for power supply and mains connections. Apply safety regulations during installation.
Install the device in a well ventilated place. Install the device permanently into a proper panel cut-out. Fix the
device with two fasteners supplied with the device. Only front panel must be accessible after installation is
completed.
Do not operate the device other then the environmental conditions given in Technical Specification.
Do not operate the device in environments that may cause conductive pollution.
Take precautions against negative environmental conditions like humidity, vibration, pollution and high/low
temperature during installation.
Use correct compensation cables for T/C sensors. Connect T/C cable directly to the device connectors.
Keep device, signal cables and communication cables away from circuit breakers, power cables and
devices/cables emitting electrical noise. Use shielded and twisted signal and communication cables and
connect shield to earth ground on device side. Keep length of signal and communication cables less than 3m.
In your applications, always use separate and independent mechanical and/or electromechanical
devices/apparatus to support DT109AX,DT107AX,DT106AX,DT105AX,DT104AX to handle emergency cases.
Use insulated cable end-sleeves at the end of cables screwed to the device connector terminals.
Maximum torque for screwing; 0.5 N.m.
Please check www.gemo.com.tr for latest device and documentation updates regularly. All updates and all
information are subject to change without notice.
This device is designed for basic temperature control applications only in light industrial environments.
PID temperature controller with OUT and ALARM outputs
Auto-tuning for PID parameters
Sensor type: T/C (J,K,T,S,R), Pt100, selectable, multi-input
Selectable control type: P, PI, PD, PID or ON-OFF
Ramp mode during power on
"Anti-windup" in PID and PI mode
Upper and Lower limit for SET and ALARM settings
Selectable relative, absolute, band or "sensor failure" alarm modes
ON-delay for OUT in cooling mode
Displays SET and PROCESS values
Cold-junction compensation for T/C
Line compensation for Pt100
Excellent linearity with o C/mV and o C/Ohm look-up tables
Input "Offset" feature
Password protection
High accuracy
EEPROM memory to store settings
Optional SSR output
Easy connection with plug-in connectors
Gürbüzoğlu Elektronik San. ve Tic. Ltd. Şti.
Çamlıtepe Cad. No:297 / 3-4 Siteler, Ankara, Türkiye
Tel: +90-312-3503900, Fax: +90-312-3511117
INSTALLATION, USE and WARNINGS
GENERAL SPECIFICATION
are suitable only for permanent panel type mounting.
2
http://www.gemo.com.tr.
e-posta: info@gemo.com.tr

Advertisement

loading

This manual is also suitable for:

Dt107axDt106axDt105axDt104ax