How Far From the Panel
Can the CRT or Printer
be Located?
The DIA has an EIA-485
Port for Terminal LCD-80
Connections. Can the
EIA-232 Terminal Con-
nection Be Used on the
SIB-NET/SIB-2048/SIB-
2048A to Program the
Panel?
30
www.PDF-Zoo.com
The UL Listed maximum distance is 50 feet. In non-listed applications, short
haul modems can be used to extend this distance. (Refer to the Installation
Manual.)
Yes. These two connectors are parallel. We recommend that during program-
ming, the LCD-80 should be disconnected to avoid unwanted interference from
terminal supervision messages sent from the LCD-80 to the fire alarm control
panel.
AM2020/AFP1010 Troubleshooting Guide 50432 Revision A 8/13/97
firealarmresources.com