Unit Charge; Cooling Only Procedure; Cooling Operation; Status Function Lights - Carrier WEATHERMAKERTM TWO-SPEED 38TDB Installation And Start-Up Instructions Manual

Two-speed air conditioning unit with puron
Hide thumbs Also See for WEATHERMAKERTM TWO-SPEED 38TDB:
Table of Contents

Advertisement

Step 11—Check Charge
Service valve gage ports are not equipped with Schrader
valves. To prevent personal injury, make sure gage manifold
is connected to the valve gage ports before moving valves off
fully back seated position. Wear safety glasses and gloves
when handling refrigerant.

UNIT CHARGE

Factory charge and charging method are shown on pink charging
label. With unit operating, charge Puron® units with liquid using
a commercial type metering device in manifold hose. Charge
refrigerant into suction line.
NOTE: Unit is to be charged in high capacity only. Charging in
low capacity may cause compressor chattering and possible
damage to the compressor.
NOTE: If subcooling charging conditions are not favorable,
charge must be weighed in accordance with unit rating plate ± 0.6
oz/ft of 3/8-in. liquid line above or below 15 ft respectively.
EXAMPLE: To calculate additional charge required for a 25-ft
line set: 25 ft - 15 ft = 10 ft X 0.6 oz/ft = 6 oz of additional charge.

COOLING ONLY PROCEDURE

1. Operate unit a minimum of 15 minutes before checking
charge.
2. Measure liquid service valve pressure by attaching an accurate
gage to service port.
3. Measure liquid line temperature by attaching an accurate
thermistor type or electronic thermometer to liquid line near
outdoor coil.
4. Refer to Table 4 for required subcooling temperature.
5. Refer to Table 3. Find the point where required subcooling
temperature intersects measured liquid service valve pressure.
6. To obtain required subcooling temperature at a specific liquid
line pressure, add refrigerant if liquid line temperature is
higher than indicated or reclaim refrigerant if temperature is
lower. Allow a tolerance of ± 3°F.
.
UNIT CHARGE
Factory charge and charging method are shown on pink charging
label. Puron® refrigerant cylinders contain a dip tube which
allows liquid refrigerant to flow from cylinder in upright
position. Charge Puron units with cylinder in upright position and
a commercial type metering device in manifold hose. Charge
refrigerant into suction line.
NOTE: Unit is to be charged in high capacity only. Charging in
low capacity may cause compressor chattering and possible
damage to the compressor.
NOTE: If subcooling charging conditions are not favorable,
charge must be weighed in accordance with unit rating plate ± 0.6
oz/ft of 3/8-in. liquid line above or below 15 ft respectively.
EXAMPLE: To calculate additional charge required for a 25 ft line
set: 25 ft - 15 ft = 10 ft x 0.6 oz/ft = 6 oz of additional charge.
Step 12—System Functions and Sequence of Operation
The outdoor unit control system has special functions. The
following is an overview of the two-speed control functions:

COOLING OPERATION

This product utilizes a 2-stage cooling indoor thermostat. With a
call for first stage cooling (Yl), the outdoor fan and low capacity
compressor are energized. If low capacity cannot satisfy cooling
demand, high capacity is energized (Yl and Y2 or Y2 only) by the
second stage of indoor thermostat. After second stage is satisfied,
Table 3—Required Liquid-Line Temperature (°F)
LIQUID
PRESSURE AT
SERVICE VALVE
(PSIG)
189
58
195
60
202
62
208
64
215
66
222
68
229
70
236
72
243
74
251
76
259
78
266
80
274
82
283
84
291
86
299
88
308
90
317
92
326
94
335
96
345
98
354
100
364
102
374
104
384
106
395
108
406
110
416
112
427
114
439
116
450
118
462
120
474
122
486
124
499
126
511
128
the unit returns to low-speed operation until first stage is satisfied
or until second stage is required again. When both first stage and
second stage cooling are satisfied, the compressor will shut off.
NOTE: If unit has not operated within the past 12 hr, or following
a unit power-up, upon the next thermostat high- or low-speed
demand, unit operates for a minimum of 5 minutes on high-speed.
NOTE: When two-speed unit is operating at low speed, system
vapor (suction) pressure will be higher than a standard single-
speed system or high-speed operation.
NOTE: Outdoor fan motor will continue to operate for one
minute after compressor shuts off, when outdoor ambient is greater
than or equal to 100°F.

STATUS FUNCTION LIGHTS

A system control STATUS function light is located on the outdoor
unit control board. (See Fig. 12.) The STATUS light provides
indication signals for several system operations. See Table 5 for
codes and definitions. Table 5 also provides the order of signal
importance.
NOTE: Only one code will be displayed on the outdoor unit
control board (the most recent, with the highest priority).
11
REQUIRED SUBCOOLING
TEMPERATURE
(°F)
8
12
14
16
18
56
54
52
50
58
56
54
52404
60
58
56
54
62
60
58
56
64
62
60
58
66
64
62
60
68
66
64
62
70
68
66
64
72
70
68
66
74
72
70
68
76
74
72
70
78
76
74
72
80
78
76
74
82
80
78
76
84
82
80
78
86
84
82
80
88
86
84
82
90
88
86
84
92
90
88
86
94
92
90
88
96
94
92
90
98
96
94
92
100
98
96
94
102
100
98
96
104
102
100
98
106
104
102
100
108
106
104
102
110
108
106
104
112
110
108
106
114
112
110
108
116
114
112
110
118
116
114
112
120
118
116
114
122
120
118
116
124
122
120
118
126
124
122
120
18
48
50
52
54
56
58
60
62
64
66
68
70
72
74
76
78
80
82
84
86
88
90
92
94
96
98
100
102
104
106
108
110
112
114
116
118

Advertisement

Table of Contents
loading

Table of Contents