Vector X2 Operation Manual page 5

Touch display
Hide thumbs Also See for X2:

Advertisement

V
ECTOR
2.7 Error messages
If an Error is active, the alarm symbol
Some errors can be confirmed by pressing the "Right" button.
Small Digits
Error condition
Err1
Communication error between operating terminal and controller
Err2
Internal error: Firmware version of the memory does not match firmware.
Err3
Internal error
Err4
Configuration error: An assigned input is not activated or has failed. Check all settings and ensure
that all inputs used are activated and functional. For TRI2 this error will show if the front panel was
removed with the internal sensor assigned to a control loop. Confirm by pressing RIGHT key.
Err5
Copy error: Communication error with external memory AEC-PM1 or AEC-PM2. The plug-in module is
either damaged or missing.
Err6
Copy error: Checksums of the data record are incorrect. The data record is invalid.
Sample display:
2.8 Status LED
Most devices have a status LED. The position of the status LED is defined in the product data sheet.
In normal operation, the LED flashes briefly once every 5 seconds.
In an alarm or error condition, the LED flashes every second.
Doc: 70-00-0951A, Serie X2, 20211220
subjects to alteration
X2-O
is set and the Error messages are shown on the small digits.
© Vector Controls GmbH, Schweiz