FG Wilson OLYMPIAN 1001 Series Manual page 16

Generating set
Table of Contents

Advertisement

FAULT
SYMPTOM
Alarm for Low
"LOW BATTERY VOLTAGE"
Battery Voltage
Alarm Lamp Illuminates
(4001 or 4001E
Series Only)
Alarm for Not in
"NOT IN AUTO MODE"
Automatic Mode
Alarm Lamp Illuminates
(4001E Series Only)
Alarm for
"APPROACHING HIGH
Approaching High
ENGINE TEMP" Alarm
Engine Temp.
Lamp Illuminates
(4001E Series Only)
Alarm for
"APPROACHING LOW OIL
Approaching Low
PRESSURE" Alarm Lamp
Oil Pressure
Illuminates
(4001E Series Only)
Alarm for Battery
"BATTERY CHARGER
Charger Failure
FAILURE" Alarm Lamp
(4001E Series Only)
Illuminates
Alarm for Low Fuel
"LOW FUEL LEVEL" Alarm
Level
Lamp Illuminates
(Optional Alarm)
Alarm for Low
"LOW COOLANT TEMP"
Coolant Temp.
Alarm Lamp Illuminates
(Optional Alarm -
2001, 4001, 4001E
Series Only)
Generating Set
Generating Set is Running
Does Not Go On
but the Load is Not Being
Load
Powered
(All control systems)
Generating Set
Generating Set Continues
Does Not Stop
Running After Being
Manually
Switched Off
(All control systems)
Generating Set
Generating Set Does Not
Does Not Stop
Stop After Remote Start
When In Auto Mode
Signal is Removed
(2001, 4001 or
4001E Series Only)
REMEDY
1. Refer to a qualified generating set technician.
1. Check Control Switch is in "AUTO".
2. Check Emergency Stop Pushbuttons are not pressed.
3. Check Circuit Breaker is on (handle up).
4. Refer to a qualified generating set technician.
1. Check engine is not overloaded.
2. Check radiator and ventilation for obstructions.
3. Refer to a qualified generating set technician.
1. Refer to a qualified generating set technician.
1. Refer to a qualified generating set technician.
1. Check fuel level in day tank. Fill as necessary.
2. Refer to a qualified generating set technician.
1. Check that the immersion heaters are switched on and are operating.
2. Refer to a qualified generating set technician.
1. Check circuit breaker is "ON" (handle up).
2. Refer to a qualified generating set technician.
1. Check Key Switch or Control Switch position, as appropriate.
2. Refer to a qualified generating set technician.
Note: On 4001 and 4001E Series Control Systems the generating set does not stop
immediately on removal of the remote start signal. Removal of this signal first initiates
the cool down period.
1. Wait 5 minutes to ensure cool down period has elapsed (4001 and 4001E Series
Control Systems only).
2. Check that generating set stops when the Emergency Stop Pushbutton is depressed
or the Control Switch is turned off.
3. Refer to a qualified generating set technician.
12