ABB VD4 Installation And Service Instructions Manual page 16

Table of Contents

Advertisement

V D 4 - INSTALLATION AND SERVICE INSTRUCTIONS
16
4. Description
4.9.1
General characteristics of withdrawable circuit breakers
for UniGear ZS1 switchgear
General characteristics of withdrawable circuit breakers
for UniGear ZS1 switchgear (12 kV)
Circuit breaker
Standards
Rated voltage
Rated insulation voltage
Withstand voltage at 50 Hz
Impulse withstand voltage
Rated frequency
Rated normal current (40 °C) (
1
)
Rated breaking capacity (rated short-circuit
breaking current symmetrical)
Rated short-time withstand current (1 s)
Making capacity
Operation sequence
Opening time
Arcing time
Total breaking time
Closing time
P
P
Maximum
overall
dimensions
D
W
Weight
Standardised table of dimensions
Operating temperature
Tropicalization
Electromagnetic compatibility
(1) 4000 A rated currentwth guaranted with forced ventilation according to ABB design
VD4/P 12
IEC 62271-100
Ur [kV] 12
Us [kV] 12
Ud (1 min) [kV] 28
Up [kV] 75
fr [Hz] 50-60
Ir [A] 1250
Isc [kA] 63
Ik [kA] 63
Ip [kA] 164
[O - 0.3 s - CO - 3 min - CO]
[ms] 28 ... 40
[ms] 10 ... 15
[ms] 38 ... 55
[ms] ≤ 55
H [mm] 736
W [mm] 750
D [mm] 646
Pole distance P [mm] 275
[kg] 261
1VCD 003943
[°C] - 5 ... + 40
IEC: 60068-2-30, 60721-2-1 •
IEC: 62271-1 •
1600
2000
2500
63
63
63
63
63
63
164
164
164
28 ... 40
28 ... 40
28 ... 40
10 ... 15
10 ... 15
10 ... 15
38 ... 55
38 ... 55
38 ... 55
≤ 55
≤ 55
≤ 55
736
736
736
750
750
750
646
646
646
275
275
275
261
261
261
3150
4000 (
1
)
63
63
63
63
164
164
28 ... 40
28 ... 40
10 ... 15
10 ... 15
38 ... 55
38 ... 55
≤ 55
≤ 55
736
736
750
750
646
646
275
275
270
270

Advertisement

Table of Contents
loading

Table of Contents