ABB VD4 Installation And Service Instructions Manual page 13

Table of Contents

Advertisement

D I S T R I B U T I O N S O L U T I O N S
4.7.2
General characteristics of fixed circuit breakers
General characteristics of fixed circuit breakers (17.5 kV)
Circuit breaker
Standards
Rated voltage
Rated insulation voltage
Withstand voltage at 50 Hz
Impulse withstand voltage
Rated frequency
Rated normal current (40 °C)
Rated breaking capacity (rated short-circuit
breaking current symmetrical)
Rated short-time withstand current (3s)
Making capacity
Operation sequence
Opening time
Arcing time
Total breaking time
Closing time
P
P
Maximum
overall
dimensions
D
W
Weight
Standardised table of dimensions
Operating temperature
Tropicalization
Electromagnetic compatibility
(1) 4000 A rated currentwth guaranted with forced ventilation according to ABB design
VD4 17.5
IEC 62271-100
Ur [kV] 17.5
Us [kV] 17.5
Ud (1 min) [kV] 38
Up [kV] 95
fr [Hz] 50-60
Ir [A] 1250
Isc [kA] 63
Ik [kA] 63
Ip [kA] 164
[O - 0.3 s - CO - 3 min - CO]
[ms] 28 ... 40
[ms] 10 ... 15
[ms] 38 ... 55
[ms] ≤ 55
H [mm] 615
W [mm] 750
D [mm] 459
Pole distance P [mm] 275
[kg] 201
1VCD 003945
[°C] - 5 ... + 40
IEC: 60068-2-30, 60721-2-1 •
IEC: 62271-1 •
1600
2000
2500
63
63
63
63
63
63
164
164
164
28 ... 40
28 ... 40
28 ... 40
10 ... 15
10 ... 15
10 ... 15
38 ... 55
38 ... 55
38 ... 55
≤ 55
≤ 55
≤ 55
615
615
615
750
750
750
459
459
459
275
275
150
201
201
201
13
3150
4000 (
1
)
63
63
63
63
164
164
28 ... 40
28 ... 40
10 ... 15
10 ... 15
38 ... 55
38 ... 55
≤ 55
≤ 55
637
637
750
750
459
459
210
275
210
210