Page 4
Electrical and electronic equipment contains materials, parts and substances, which can be dangerous to the environment and harmful to human health if the waste of electrical and electronic equipment (WEEE) is not disposed of correctly. ECS Series Manual — P/N LS10262-001FK-E:A 3/3/2021...
FIK-RA2000 (Remote Annunciator) FIK-LOC2100 FIK-RVM (Remote Voice Module) FIK-RA2000 (Remote Annunciator) 1.1 Optional Accessories This manual also contains information on how to install the following compatible accessory with the ECS series equipment: Model Number Description Compatible With FIK-SW24 Adds 24 additional switches to the FIK-NVCM or FIK-RVM to...
Notification functionality as described in UL standard 2572. FACP Fire Alarm Control Panel Local Operator's Console: The user interface for a Mass Notification System. In the Fike Series product line, this would be the interface provided by the FCP-300ECS or FCP-2100ECS. Mass Notification A way of protecting life by relaying specific event information to a building or site including voice and/or audible and visual signals.
Page 9
Notes ECS Series Manual — P/N LS10262-001FK-E:A 3/3/2021...
If using wired Ethernet, you must program the corresponding account/subscriber ID and a test time so that the FACP shall automatically initiate a test signal transmission sequence to its associated receiver at least once every 6 hrs. ECS Series Manual — P/N LS10262-001FK-E:A 3/3/2021...
The AC Loss Hours option must be set from 1-3 hours. 2.2.5 Requirements for the Installation of Carbon Monoxide (CO) Detection and Warning Equipment, NFPA 720 When using carbon monoxide detection the system must be monitored by a supervising station. ECS Series Manual — P/N LS10262-001FK-E:A 3/3/2021...
Section 3: Installation This section of the manual is intended to help you plan your tasks to complete the installation. Please read this section thoroughly, especially if you are installing a ECS Series control panel for the first time. 3.1 Environmental Specifications It is important to protect the ECS panel from water.
Page 13
Wiring Specifications Installation AC Power Input SBUS devices devices Phone Lines Figure 3.1 Wire Routing FCP-300ECS ECS Series Manual — P/N LS10262-001FK-E:A 3/3/2021...
240V 50/60 Hz 260 mA 1525 mA FIK-DUAL50W 70V 120V 60 Hz 210 mA 2650 mA FIK-DUAL50W 70V 240V 50/60 Hz 260 mA 1600 mA Table 3.3 FIK-DUAL50W AC Current Draw Fully loaded system ECS Series Manual — P/N LS10262-001FK-E:A 3/3/2021...
Installation 3.4 Installing ECS Series Cabinets This section provides instructions on how to install the ECS series cabinets for surface or flush mounting. 3.4.1 Preventing Water Damage Refer to Section 3.1 when choosing a mounting location. Water damage to the fire system can be caused by moisture entering the cabinet through the conduits.
FCP-300. For more information, refer to Installation manuals for the FACP. Cabinet dimensions are 20.362" W x 27" H x 5.054" D. Key Shaped Holes 27" Bottom Mounting Holes 20.362" Figure 3.4 FIK-LOC Cabinet Mounting Holes ECS Series Manual — P/N LS10262-001FK-E:A 3/3/2021...
Figure 3.5 FCP-300ECS Cabinet Mounting Holes 3.4.5 Surface Mounting the FCP-2100ECS or FIK-LOC2100 Cabinet The FIK-LOC2100 is a combination FIK-RVM Remote Voice Module and its associated FIK-RA2000 annunciator. The FIK-LOC2100 is compatible with the FCP-2100ECS. ECS Series Manual — P/N LS10262-001FK-E:A 3/3/2021...
3.4.6 Surface Mounting Instructions The ECS Series cabinets can be mounted on the wall surface by using the mounting holes in the back of the cabinet (see Figure 3.7). Insert two screws level with each other, 16" apart for the top cabinet key shaped holes. See Figure 3.7.
Page 19
Hinge Pin Dead Front Panel Cabinet Door Figure 3.7 Cabinet Door and Dead Front Panel Removal To re-attach the cabinet door, the top hinge should be aligned first, followed by the lower hinge. ECS Series Manual — P/N LS10262-001FK-E:A 3/3/2021...
For more information on how to install or remove the FIK-NVCM Network Voice Control Module, see installation sheet PN LS10169-002FK-E. 4.2.1 FIK-NVCM Board Layout Network Connector P4 Keypad connector P3 AUX AUDIO VBUS1 CMD1 COMMON Fiber CMD2 Module Connectors Port 2 VBUS2 Port 1 Figure 4.1 Front View of FIK-NVCM ECS Series Manual — P/N LS10262-001FK-E:A 3/3/2021...
The FIK-SW24 adds 24 switches to the FCP-300ECS and FCP-2100ECS controls for a total of 40, with the 16 Non-ECS switches on the FIK-EMG. Follow these steps to install and connect the FIK-SW24: Open Cabinet door and dead front panel. Remove AC power from the main control panel. Disconnect the backup batteries. ECS Series Manual — P/N LS10262-001FK-E:A 3/3/2021...
Page 22
Secure the switch expander(s) to the dead front panel using the supplied six ¼” Hex nuts. Restore AC power. Reconnect backup batteries FACP NVCM Figure 4.4 Wiring Harness Connection for the FIK-NVCM to the FCP-300ECS Figure 4.5 Connection between the FIK-EMG and One FIK-SW24 ECS Series Manual — P/N LS10262-001FK-E:A 3/3/2021...
Page 23
Installing the FIK-NVCM Device Installation Figure 4.6 Wiring Harness Connection for the FIK-NVCM to FCP-2100ECS Figure 4.7 Connection between FIK-EMG and Two FIK-SW24s ECS Series Manual — P/N LS10262-001FK-E:A 3/3/2021...
FIK-FSL (Fiber-Optic Single-Mode, Transmitter) 4.2.4 Installing the Microphone To install the microphone follow these steps: Clip the microphone into the micro phone clip. See Figure 4.8. Figure 4.8 Hang Microphone on to Microphone Clip ECS Series Manual — P/N LS10262-001FK-E:A 3/3/2021...
Connect microphone to appropriate connector on FIK-EMG. 2¾" Figure 4.10 Installing Strain Relief Clip 4.3 Installing the FIK-50W This section provides information on how to install the FIK-50W for use with the ECS Series products. ECS Series Manual — P/N LS10262-001FK-E:A 3/3/2021...
H x 3-7/16” D (36.8cm W x 62.9cm H x 8.73cm D). Do not flush-mount in a wall designated as a fire break. The outside dimensions of the cabinet are 16" W x 26½” H x 4-1/8” D (40.64cm W x 66.68cm H x 10.48cm D). ECS Series Manual — P/N LS10262-001FK-E:A 3/3/2021...
For the same reasons, wiring within the cabinet should be routed around the perimeter of the cabinet. It should not cross the printed circuit board where it could induce noise into the sensitive microelectronics or pick up unwanted RF noise from the high speed circuits. ECS Series Manual — P/N LS10262-001FK-E:A 3/3/2021...
25Vrms 1130 1800 70Vrms 3500 5560 8850 14070 NOTE: The above table assumes a uniform distribution of the speakers, and that a max of 20% voltage drop on the last speaker is allowed ECS Series Manual — P/N LS10262-001FK-E:A 3/3/2021...
The VBUS is an analog voice bus that carries the recorded voice messages from the FIK-NVCM to the FIK-50W, or the voice messages gen- erated from a system microphone to the FIK-50W. The maximum resistance on the VBUS is 20Ω. Connect the VBUS from the FIK-NVCM as shown in Figure 4.16. ECS Series Manual — P/N LS10262-001FK-E:A 3/3/2021...
This section contains information on how to connect FIK-50Ws (up to 8 for FCP-300ECS or up to 16 for FCP-2100ECS) onto the main con- trol SBUS. Refer to Section 4.1 for SBUS specifications. Wire the SBUS as shown in Figure 4.17 or Figure 4.18. Control Panel Figure 4.17 SBUS Connections of the FIK-50W ECS Series Manual — P/N LS10262-001FK-E:A 3/3/2021...
To access cabinet interior, open dead-front panel by removing the upper screw and the mid-door retaining screw. Mount the transformer onto the threaded cabinet transformer mounting studs using the supplied locking hex nuts as shown in Figure 4.19. Threaded mounting studs Figure 4.19 Transformer Mounting ECS Series Manual — P/N LS10262-001FK-E:A 3/3/2021...
Connect the black wire of the battery harness to the (-) side of the battery #2. Connect the jumper wire provided form the positive (+) side of battery #2 to the negative side of battery #1. ECS Series Manual — P/N LS10262-001FK-E:A 3/3/2021...
Alarm sounding period in hours (For example, 5 minutes = 0.0833 hours): Multiply line C (alarm current) and F: Total alarm AH Add lines E and G (AH = Ampere Hours): Total AH required Table 4.1 Current Draw FIK-50W and FIK-CE4 ECS Series Manual — P/N LS10262-001FK-E:A 3/3/2021...
4.4 Installing the FIK-INT50W This section provides information on how to install the FIK-INT50W for use with the ECS Series products. The FIK-INT50W Internal Amplifier can fit inside the FCP-300ECS cabinet. It can also be adapted to fit into the FCP-2100ECS cabinet with the FIK-AMPMT mount- ing kit (sold separately).
Page 35
FIK-INT50W onto the six standoffs, making sure the two coil parts are at the top, and on the right side of the FIK-AMPMT. See Figure 4.25 and Figure 4.25 for coil position. "Top" FIK-AMPMT Mounting Holes Figure 4.24 FIK-AMPMT installed in Cabinet Figure 4.25 FIK-INT50W Installed using the FIK-AMPMT ECS Series Manual — P/N LS10262-001FK-E:A 3/3/2021...
See Figure 4.27 to properly wire the FIK-INT50W to the FACP. The Internal Amplifier must be powered by a NAC programmed as Constant Auxiliary Power. Refer to the FACP installation manual. FIK-INT50W FACP Figure 4.27 Wiring the FIK-INT50W to the FACP ECS Series Manual — P/N LS10262-001FK-E:A 3/3/2021...
Current Per Device Devices Current Current FIK-INT50W 25V Standby: 52 mA 52mA Alarm: 275 mA 275mA FIK-INT50W 70V Standby: 52 mA 52mA Alarm: 310 mA 310mA Current Subtotals: Table 4.2 Current Draw Calculations ECS Series Manual — P/N LS10262-001FK-E:A 3/3/2021...
Table 4.2 Current Draw Calculations 4.6 Installing the FIK-125W This section provides information on how to install the FIK-125W for use with Fike ECS series products. 4.6.1 FIK-125W Board Layout Figure 4.29 on page 38 shows the location of terminals, DIP switches, and expander connections used in the installation of the FIK-125W.
Make certain that AC and DC power have been removed from the panel. If this module is a replacement for an existing FIK-125W, remove the screws which secure the board to the enclosure. ECS Series Manual — P/N LS10262-001FK-E:A 3/3/2021...
Life Safety Code (NFPA 101). To avoid induced noise (transfer of electrical energy from one wire to another), keep input wiring isolated from high-current output and power wiring. Avoid pulling one multi-conductor cable for the entire panel. ECS Series Manual — P/N LS10262-001FK-E:A 3/3/2021...
Each FIK-125W supplies four NACs (Notification Appliance Circuits) for speaker connection. The speaker circuit can be supervised and wired Class B or Class A. Speaker circuit 1 is capable of 100 watts of power at 25 Vrms. Speaker circuit 2-4 are capable of 50 watts (each) at 25 Vrms. ECS Series Manual — P/N LS10262-001FK-E:A 3/3/2021...
Page 42
Figure 4.34 Class B Speaker Configuration Class A Figure 4.35 illustrates how to wire speakers to the control panel using Class A wiring. Supervised power limited Figure 4.35 Class A Speaker Configuration ECS Series Manual — P/N LS10262-001FK-E:A 3/3/2021...
This section contains information on how to connect FIK-125Ws (up to 8 for FCP-300ECS; up to 16 for FCP-2100ECS) onto the main con- trol SBUS. Refer to Section 4 of the FACP’s Installation manual for SBUS specifications. Wire the SBUS as shown in Figure 4.37 or Figure 4.37 for the FIK-NVCM. ECS Series Manual — P/N LS10262-001FK-E:A 3/3/2021...
See Section 4.11 for information on setting SBUS addresses. 4.6.8 Connecting AC Power At installation, connect the AC terminals to the power source as shown in Figure 4.39. It may be necessary for a professional electrician to make this connection. ECS Series Manual — P/N LS10262-001FK-E:A 3/3/2021...
4.6.10 Calculating Current Draw and Standby Battery This section helps you determine the current draw and standby battery needs for your installation (18 Ampere Hours maximum will fit in cabinet). Complete the remaining instructions in Table 4.4. ECS Series Manual — P/N LS10262-001FK-E:A 3/3/2021...
Table 4.4 Current Draw FIK-125W 4.7 Installing the FIK-DUAL50W/HV This section provides information on how to install the FIK-DUAL50W for use with the FCP-300ECS and FCP-2100ECS. The FIK-DUAL50W is available with 240VAC input as FIK-DUAL50WHV. ECS Series Manual — P/N LS10262-001FK-E:A 3/3/2021...
24.75" H x 3-7/16” D (36.8cm W x 62.9cm H x 8.73cm D). Do not flush-mount in a wall designated as a fire break. The Outside dimensions of the cabinet are 16.1" W x 26 ½” H x 4-1/8” D (40.64cm W x 66.68cm H x 10.48cm D). ECS Series Manual — P/N LS10262-001FK-E:A 3/3/2021...
Make certain that AC and DC power have been removed from the panel. If this module is a replacement for an existing FIK-DUAL50W, remove the screws which secure the board to the enclosure. ECS Series Manual — P/N LS10262-001FK-E:A 3/3/2021...
1/4” spacing must be maintained Input/Output Type: Wiring between each of these circuit types; Non Power-Limited: AC power, Standby batteries as well as between power limited Power-Limited: SBUS, VBUS and non power-limited circuits. Audio: Speaker ECS Series Manual — P/N LS10262-001FK-E:A 3/3/2021...
Each FIK-DUAL50W supplies eight NAC (Notification Appliance Circuit) for speaker connection. The speaker circuit can be supervised and wired Class B or Class A. The speaker circuits are capable of 50 watts (each) at 25 Vrms or 70.7 Vrms. ECS Series Manual — P/N LS10262-001FK-E:A 3/3/2021...
Page 51
NOTE: The above table assumes a uniform distribution of the speakers, and that a max of 20% voltage drop on the last speaker is allowed Class B Speaker Configuration for FIK-DUAL50W Figure 4.46 illustrates how to wire speakers to the control panel using Class B supervision. Supervised power limited 15kΩ EOL Figure 4.46 Class B Speaker Configuration ECS Series Manual — P/N LS10262-001FK-E:A 3/3/2021...
The FIK-DUAL50W supports two VBUS channels. The wiring method is the same for both channels. VBUS1 and VBUS2 should never be wired together. Connect the VBUS from the Figure 4.48 and Figure 4.49 for FIK-NVCM. ECS Series Manual — P/N LS10262-001FK-E:A 3/3/2021...
Page 53
Installing the FIK-DUAL50W Device Installation FIK-NVCM FIK-DUAL50W FIK-DUAL50W Figure 4.48 VBUS Wiring for Single Channel for FIK-NVCM FIK-DUAL50W FIK-DUAL50W FIK-NVCM Figure 4.49 VBUS2 Wiring for Dual Channel for FIK-NVCM ECS Series Manual — P/N LS10262-001FK-E:A 3/3/2021...
Figure 4.51 using the FIK-NVCM. FACP Figure 4.50 SBUS Connections to the FIK-DUAL50W FACP FIK-DUAL50W FIK-NVCM To next FIK-DUAL50W Figure 4.51 SBUS Connections to Multi FIK-DUAL50Ws See Section 4.11 for information on setting SBUS addresses. ECS Series Manual — P/N LS10262-001FK-E:A 3/3/2021...
At installation, connect the AC terminals to the power source as shown in Figure 4.53. It may be necessary for a professional electrician to make this connection. The AC terminals are rated as 120VAC, 60 Hz or 240VAC, 50/60 Hz. Figure 4.53 AC Connection ECS Series Manual — P/N LS10262-001FK-E:A 3/3/2021...
The FIK-50WBU provides backup capability when operating the FIK-DUAL50W in the 100 watt with backup mode for both single and dual channel setups. The FIK-50WBU mounts above the FIK-DUAL50W board on the standoffs provided. ECS Series Manual — P/N LS10262-001FK-E:A 3/3/2021...
Make sure that all power supplied to the FIK-DUAL50W is removed. Connect the backup amplifier cable harness (P/N 50116775-001) from the connector labeled “Backup Amplifier” on the FIK- DUAL50W to the connector on the FIK-50WBU as shown in Figure 4.56. ECS Series Manual — P/N LS10262-001FK-E:A 3/3/2021...
FIK-50WBU Standoff cable harness Figure 4.56 Mounting the FIK-50WBU 4.9 Installing the FIK-CE4 The FIK-CE4 adds four audio circuits to the FIK-50W and FIK-125W. The FIK-CE4 mounts inside the FIK-50W or FIK-125W cabinet. ECS Series Manual — P/N LS10262-001FK-E:A 3/3/2021...
The FIK-RVM Remote Voice Module is contained within the FIK-LOC or FIK-LOC2100 Local Operator Console. It provides a supervised microphone for live communication and an interface for the Emergency Communication System. 4.10.1 FIK-RVM Board Layout The following is description of the FIK-RVM remote voice module components. ECS Series Manual — P/N LS10262-001FK-E:A 3/3/2021...
Figure 4.59 Back View of FIK-RVM 4.10.2 Wiring the FIK-RVM Refer to Figure 4.60 to properly connect the FIK-RVM to the FACP’s SBUS. FIK-RVM Supervised power limited FACP Figure 4.60 SBUS Connections ECS Series Manual — P/N LS10262-001FK-E:A 3/3/2021...
Page 61
Set the SBUS address on the annunciator and the FIK-RVM board. See Section 4.11. Connect the FIK-RVM to the VBUS, FIK-125W, and FIK-NVCM. See Figure 4.62. FIK-NVCM FIK-RVM FIK-125W Figure 4.62 VBUS and FIK-125W Wiring for FIK-RVM using the FIK-NVCM ECS Series Manual — P/N LS10262-001FK-E:A 3/3/2021...
Figure 4.64 Microphone Cord Inserted Through Dead Front Panel Hole Attach strain relief clip to microphone cord. The strain relief clip should have about 2¾” of micro phone cord through it. See Figure 4.65. 2-3/4” Figure 4.65 Installing Strain Relief Clip ECS Series Manual — P/N LS10262-001FK-E:A 3/3/2021...
When installing a hardware module (such as FIK-6815, FIK-5824, FIK-RA1000, FIK-RA100, FIK-RA2000, FIK-5496, FIK-RPS-1000, FIK-5865-3 or FIK-5865-4, FIK-50W, FIK-125W, FIK-DUAL50W, FIK-NVCM and FIK-RVM), you must use the DIP switches on the module to assign an ID# to the module. ECS Series Manual — P/N LS10262-001FK-E:A 3/3/2021...
Page 64
Figure 4.67 Possible Module Addresses More information regarding ECS operations, Please refer to the ECS section of the FACP’s installation manual. ECS Series Model Number FACP Installation Manual FCP-300ECS LS10145-002FK-E FCP-2100ECS LS10143-002FK-E ECS Series Manual — P/N LS10262-001FK-E:A 3/3/2021...
Page 65
ECS Series Manual — P/N LS10262-001FK-E:A 3/3/2021...
Page 66
FIKE CORPORATION 704 SW 10th Street Blue Springs, MO 64015 Telephone: +1-816-229-3405 www.fike.com...