Carrier ZONECC3Z Installation And Start-Up Instructions Manual

Carrier ZONECC3Z Installation And Start-Up Instructions Manual

3-zone system

Advertisement

Visit www.carrier.com
Installation and Start-Up Instructions

TABLE OF CONTENTS

SAFETY CONSIDERATIONS...................................................1
INSTALLATION CONSIDERATIONS....................................1
INTRODUCTION ........................................................................1
INSTALLATION ......................................................................1-4
• Check Equipment And Job Site ..............................................1-2
• Install Components......................................................................2
• Install Zone Dampers...............................................................2-4
• Install Barometric Bypass Damper .............................................4
SYSTEM WIRING ...................................................................4-5
• Wire Thermostats ........................................................................4
• Wire Equipment...........................................................................4
• Wire Dampers..............................................................................5
• Wire Remainder...........................................................................5
UNDERSTANDING SYSTEM OPERATION ......................6-7
SYSTEM SETUP ....................................................................7-10
NOTE: Read the entire instruction manual before starting the

installation.

SAFETY CONSIDERATIONS

Improper installation, adjustment, alteration, service, maintenance,
or use can cause fire, electrical shock, or other conditions which
may cause personal injury or property damage. Consult a qualified
installer, service agency or your distributor or branch for informa-
tion or assistance. The qualified installer or agency must use
factory-authorized kits or accessories when modifying this prod-
uct. Refer to the individual instructions packaged with the kits or
accessories when installing.
Follow all safety codes and wear safety glasses. Have fire
extinguisher available. Read these instructions thoroughly and
follow all warnings or cautions attached to the unit. Consult local
and state building codes and Sheet Metal and Air Conditioning
National Association (SMACNA) for special installation require-
ments.
Recognize safety information. This is the safety-alert symbol
When you see this symbol on the unit or in instructions and
manuals, be alert to the potential for personal injury.
Understand the signal words DANGER, WARNING, and CAU-
TION. These words are used with the safety-alert symbol. DAN-
GER identifies the most serious hazards which will result in severe
personal injury or death. WARNING signifies hazards which
could result in personal injury or death. CAUTION is used to
identify unsafe practices which would result in minor personal
injury or product and property damage. NOTE is used to highlight
suggestions which will result in enhanced installation, reliability,
or operation.

INSTALLATION CONSIDERATIONS

Before the actual installation of a zoning system can begin,
decisions need to be made to determine the number and location of
zones. This affects duct and damper selections.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 1 4 4
PC 101
Tab 3a 5a 2a 5a
Page
Catalog No. 809-50009
Printed in U.S.A.
This instruction covers the physical installation and start up of the
Carrier 3-Zone system. Use this instruction to guide the actual
installation process after all the air side decisions have been made.
1. Install in non-condensing areas with ambients between 32°F
and 158°F.
2. A TXV is required on the indoor coil when used with all
residential split system equipment.
3. A separate transformer is not needed to power the 3-Zone
system. Up to five dampers may be used in each zone by
electrically connecting them in parallel.
4. Load calculations must be performed for each zone's peak
demand. Size each zone duct for at least its peak demand plus
25%. Size equipment for the building block load, not the sum
of zone peak demands. It is important that the equipment not
be oversized.
5. When only two zone operation is needed, any two of the three
zone connections may be used. There is no inherent priority
dependent on zone number.
UNIT DAMAGE HAZARD
Failure to follow this caution may result in unit damage.
TXV on indoor coil is required with all residential split
system equipment.
The Carrier 3-Zone system allows the air conditioning and heating
equipment to control temperatures in 3 distinct spaces or zones
within a building. Each zone has independent temperature settings
controlled by a conventional thermostat.
There are two distinct controllers:
• ZONECC3ZAC01 - Single Stage Heat / Single Stage Cool
using conventional single stage thermostats.
• ZONECC3ZHP01 - Three Stage Heat / Two Stage Cool
compatible for HP and multi-stage application thermostats and
equipment.
.
Each system controller is comprised of a three-zone controller and
a duct temperature sensor.
NOTE: Thermostats are purchased separately.
The comfort temperature settings can change automatically
through the use of schedules if programmable thermostats are
selected. This allows the Carrier 3-Zone to change the temperature
settings in zones to reflect occupancy or usage. The Carrier 3-Zone
system uses motorized air volume control dampers (also called
zone dampers) to regulate the flow of conditioned air into the
zones.
Step 1-Check Equipment and Job Site
INSPECT EQUIPMENT - File claim with shipping company,
prior to installation, if shipment is damaged or incomplete.
Form ZONEKIT-15SI
ZONECC3Z(AC/HP)01

INTRODUCTION

INSTALLATION
Pg 1
11-04
Replaces: NEW

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the ZONECC3Z and is the answer not in the manual?

Questions and answers

Summary of Contents for Carrier ZONECC3Z

  • Page 1: Table Of Contents

    This allows the Carrier 3-Zone to change the temperature settings in zones to reflect occupancy or usage. The Carrier 3-Zone system uses motorized air volume control dampers (also called zone dampers) to regulate the flow of conditioned air into the zones.
  • Page 2: Component Location And Wiring Considerations

    Step 3—Install Components INSTALL CARRIER 3-ZONE SYSTEM The Carrier 3-Zone System is designed so that wires can enter it from behind, above, or below. Plan wire routing before mounting. 1. Open door to access eight mounting screw slots 2.
  • Page 3 need not be perfect because there will be positive pressure inside the cover. Do not mount the dampers with their actuators hanging directly beneath the ductwork. It is best to mount the actuator facing in either the three or nine o’clock position. For specific duct types, follow instructions below: ROUND METAL DUCT WORK 1.
  • Page 4: Install Barometric Bypass Damper

    1 or 2 stage heating applications. For 2 stage heating, the stat may be a 2 stage heat AC stat or a HP stat converted to AC. (Carrier HP stats can be field converted to 2 stage heat AC stats.) Fig.
  • Page 5: System Wiring

    To 24VAC Power Rc/Rh Twist Of f To Equipment CLS_1 To Zone 1 COM_1 Damper OPN_1 CLS _ 2 To Zone 2 COM_2 Damper OPN _ 2 CLS _ 3 To Zone 3 COM_3 Damper OPN _ 3 LA T To LAT LA TC Sensor...
  • Page 6: Understanding System Operation

    UNDERSTANDING SYSTEM OPERATION (READ BEFORE STARTING SYSTEM) Mode and Damper Positions The thermostats determine the system heating or cooling mode. The first call in any zone sets the mode to satisfy that call. It will remain in that mode until all calls in that mode are satisfied and the equipment has been off for the time set by the auto changeover time dipswitches.
  • Page 7: System Setup

    Table 2—Limit Temperature Levels and Actions LIMIT LEVEL Cooling Limit (40 deg) above HP limit (115 deg) below Heat Limit (130 deg) below Heat Limit (145 deg) below Heat Limit (160 deg) below Heat Limit (175 deg) below LIMIT ACTIONS ″Closed″...
  • Page 8 not bring on G with W. Default is OFF. Dipswitch 7 and 8 - Sets LAT limit temperature. See LAT Limit Selection for proper setting. Default is OFF = 145° limit. The following dipswitches are on the HP/2S control only: Dipswitch 9 - Informs the control whether it is connected to a heat pump or an air conditioner.
  • Page 9 ZONE 1 ZONE 1 AC TSTAT INPUT Y/Y2 COOL HEAT AC 3-ZONE CONTROL Fig. 10 — AC 3-Zone Control, AC STAT, 1-Stg. AC with 1-Stg. Heat ZONE 1 ZONE 1 INPUT AC TSTAT Y/Y2 COOL (LO) HEAT SWITCH 9=ON SWITCH 10=ON (HI HEAT) HP/2S 3-ZONE CONTROL Fig.
  • Page 10 ZONE 1 ZONE 1 INPUT AC TSTAT COOL Y/Y2 HP HEAT SWITCH 9=OFF SWITCH 10=ON AUX HEAT H P/2S 3-ZONE CONTROL Fig. 13 — HP/2S 3-Zone Control, AC Stat, 1-Stg. HP with 1-Stg. Aux. Heat ZONE 1 ZONE 1 INPUT 2S AC TS TAT LO COOL (LO) HEAT...
  • Page 12: Service Training

    [ ] Packaged Service Training [ ] Classroom Service Training Copyright 2004 CARRIER Corp. • 7310 W. Morris St. • Indianapolis, IN 46231 Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.