Lamp Test; Fig. 8-1 Local Operator Panel - ABB ACS5000 User Manual

Medium voltage ac drive air-cooled, 2 - 7 mva
Hide thumbs Also See for ACS5000:
Table of Contents

Advertisement

ABB
3
5
Fig. 8-1
Local operator panel
8.4.1

Lamp test

5k A UM
1
2
6
4
7
For further information on the CDP control panel, see
control
panel.
The lamp test is activated via the CDP control panel by setting parameter
16.7 to LAMP TEST. The lamp-test resets itself after a set time.
3BHS221906 ZAB E01 Rev. D
1
CDP control panel
Main functions:
■ Starts and stops the motor
■ Displays status messages of the drive
Displays alarm and fault messages of the drive and
monitored foreign equipment.
Resets alarm and fault messages
2
Main power supply on
When pressed, the illuminated pushbutton charges
the DC link, and closes the main circuit breaker.
3
Main power supply off
When pressed, the illuminated pushbutton opens the
main circuit breaker.
4
Emergency-off reset pushbutton
Resets the emergency-off relay of the drive control
system.
Flashes when the auxiliary voltage is switched on, or
when an emergency-off switch is pressed.
5
Alarm / Fault lamp
■ Alarm: flashing light
■ Fault: permanent light
6
Grounding switch unlocked
Lights up to indicate that the grounding switch of the
drive can be turned to the grounded or ungrounded
position.
7
Emergency-off
Latching pushbutton, prevents starting when pressed
at standstill of the drive.
When pressed during operation of the drive, the main
circuit breaker opens immediately and the DC link
discharges.
Chapter 8 - Operation
Chapter 9 - CDP
8-3 (14)