CAUTION
DO NOT store or install units in corrosive environments or
in locations subject to temperature or humidity extremes
(e.g., attics, garages, rooftops, etc.). Corrosive conditions
and high temperature or humidity can significantly reduce
performance, reliability, and service life. Always move
units in an upright position. Tilting units on their sides may
cause equipment damage.
INSPECT UNIT — To prepare the unit for installation, com-
plete the procedures listed below:
1. Compare the electrical data on the unit nameplate with
ordering and shipping information to verify that the
correct unit has been shipped.
2. Verify that the unit is the correct model for the entering
water temperature of the job.
3. Do not remove the packaging until the unit is ready for
installation.
4. Verify that the refrigerant tubing is free of kinks or dents,
and that it does not touch other unit components.
UNIT 50RTP
Compressor (qty)
Factory Charge R-410A (oz)
Blower Motor
Motor Quantity
Standard Motor (hp)
Large Motor (hp)
Blower(s)
Number of Blowers
Blower Wheel Size (dia x w)
V-belt size, Std drive
Water Connection Size
IPT (in.)
Coax Volume
Volume (US Gallons)
Condensate Connection Size
FPT (in.)
Air Coil Data
Air Coil Total Face Area (sq ft)
Filter, Standard, Qty...Size (in.)
Operating Weight (lb)
Shipping Weight (lb)
Corner Weights (lb)
Front-Left
Front-Right
Rear-Left
Rear-Right
Curb, Installed (lb)
IPT — Iron (National) Pipe Thread
Table 1 — Physical Data — Aquazone™ 50RTP03-20 Units
03
04
05
Scroll (1)
64
84
120
1
1
1
N/A
1.5
1.5
10 x 6
A29
A30
A32
3
/
1
4
0.61
0.77
1.11
5
4...16 x 20
735
785
835
750
800
850
184
196
208.5
259
276
293.5
108.5
117
124.5
183.5
196
208.5
83
5. Inspect all electrical connections. Be sure connections are
clean and tight at the terminals.
6. Compressors are internally spring-mounted. Compressors
equipped with external spring vibration isolators must
have bolts loosened and shipping clamps removed.
7. Remove any blower support cardboard from inlet of the
blower if present.
8. Locate and verify any accessory kit located in compressor
section.
9. Remove any access panel screws that may be difficult to
remove once unit is installed.
Step 3 — Locate Unit —
should be considered when choosing a location for WSHP. Re-
fer to Fig. 1-3 for unit dimensional data. See Fig. 4 for accesso-
ry roof curb dimensional data.
• Provide sufficient space for water, electrical and duct
connections
• Locate unit in an area that allows for easy access and
removal of filter and access panels
• Allow enough space for service personnel to perform
maintenance
06
08
132
108
1
1.5
2
2
3
1
2 x 12
15 x 11
AX33
B40
1
1
/
4
1.30
1.69
1
7
9.33
6...16 x 20
880
1080
900
1100
224
292
298
380
134
193
224
215
3
The
following
10
12
14
Scroll (2)
120
130
192
3
3
3
5
5
5
15 x 15
15 x 11
BX42
BX46
B39
1
1
/
2
2.29
2.68
3.83
10.5
8...16 x 20,
2...20 x 20
1125
1175
1770
1150
1200
1800
303.5
320
479
395.5
406
623
202
212.5
315
224
236.5
353
94
guidelines
20
300
5
7.5
2
BX40
2
4.77
20
1960
2000
530
690
350
390
128