4.4.2 Connecting AC Input Power Cables

Figure 4-9 Connecting AC input power cables
Issue 05 (2021-11-16)
Figure 4-8 Connecting DC output cables and signal cables (crimped)
The metal socket is delivered with the AC input connector.
Check whether the metal socket is reliably crimped. The minimum pull-out
force is 400 N for 8 AWG cables or cables with a cross-sectional area of 10
2
mm
.
The front end of the heat-shrink tubing should not exceed the scale on the
metal socket. The outer diameter of the metal socket covered with the heat-
shrink tubing is less than or equal to 7.5 mm.
Copyright © Huawei Digital Power Technologies Co., Ltd.