Mitsubishi Electric LGH-F300RX3-E Handbook page 21

Lossnay energy recover ventilator
Hide thumbs Also See for LGH-F300RX3-E:
Table of Contents

Advertisement

2Temperaturers vs. thermistor resistance table
Temperature
Resistance
(°F)
value (kΩ)
88.85 - ∞
-40
-4
32.43
-2.2
30.92
-0.4
29.50
1.4
28.14
3.2
26.87
5
25.65
6.8
24.51
8.6
23.42
10.4
22.39
12.2
21.41
14
20.48
15.8
19.58
17.6
18.73
Temperature
Resistance
(°F)
value (kΩ)
19.4
17.92
21.2
17.16
23
16.43
24.8
15.74
26.6
15.08
28.4
14.45
30.2
13.86
32
13.29
33.8
12.74
35.6
12.22
37.4
11.72
39.2
11.25
41
10.80
42.8
10.37
44.6
9.96
Temperature
Resistance
(°F)
value (kΩ)
46.4
9.57
48.2
9.20
50
8.84
51.8
8.49
53.6
8.17
55.4
7.85
57.2
7.55
59
7.27
60.8
6.99
62.6
6.73
64.4
6.48
66.2
6.24
68
6.01
69.8
5.79
71.6
5.58
— 21 —
Temperature
Resistance
(°F)
value (kΩ)
73.4
5.38
75.2
5.19
77
5.00
78.8
4.82
80.6
4.65
82.4
4.49
84.2
4.33
86
4.18
87.8
4.03
89.6
3.89
91.4
3.76
93.2
3.63
95
3.51
96.8
3.39
98.6
3.28
Temperature
Resistance
(°F)
value (kΩ)
100.4
3.17
102.2
3.06
104
2.96
105.8
2.86
107.6
2.77
109.4
2.68
111.2
2.59
113
2.51
114.8
2.43
116.6
2.35
118.4
2.28
120.2
2.21
122
2.14
189.5
0.72 - 0

Advertisement

Table of Contents
loading

This manual is also suitable for:

Lgh-f600rx3-eLgh-f1200rx3-e

Table of Contents