Download Print this page
NK TECHNOLOGIES DS3 Series Instructions

NK TECHNOLOGIES DS3 Series Instructions

Dc current operated switch

Advertisement

Quick Links

Specifications
Power
20-28 VAC/DC, 10 VA
Setpoint Ranges
4-20A, 10-50A, 20-100A
Setpoint Adjust
11 Turn potentiometer
Isolation Voltage
1.48KV
Frequency Range
DC to 400 Hz
Repeatability
0.5%
Hysteresis
5% of setpoint
Sensing Aperture
0.75" (19mm)
Case
UL 94-V0 Flammability Rated
Output Rating & Environmental
NOU
Isolated Solid State Switch
0.3A @ 135 VAC/DC
Off State Leakage
NONE
Environmental
-40 to 60 DegF (-40 to 140 DegF)
0-95% RH, Non Condensing
SDT
SPDT (Form C) Relay
5A General Purpose @ 240 VAC
3A Inductive @ 240 VAC
3A @ 30 VDC
1/8HP @ 240 VAC
Environmental
-20 to 50 DegC (-4 to 122 DegF)
0-95% RH, Non Condensing
Ranges & Maximum Amps
RANGE
RANGE
MAX
SOLID CORE
JUMPER
5 SEC.
4-20 A
LOW
At least
10-50 A
MID
1000% of
20-100 A
HIGH
Range
Model Number Key
DS3 - SDT - 24U
OUTPUT:
NOU Normally Open Solid State Switch, 0.3A
SDT
SENSOR TYPE:
DS3 DC current sensing switch with 3 jumper selectable
range and adjustable setpoint
Know Your Power
MAX
CONTINUOUS
Other NK Technologies Products Include:
AC & DC Current Transducers
At least 200%
of range
AC & DC Current Operated Switches
indefinely
1φ & 3φPower Transducers
Current & Potential Transformers (CTs&PTs)
500 Division Street, Campbell CA 95008
800-959-4014 or +1-408-871-7510 Phone
+1-408-871-7515 FAX
sales@nktechnologies.com, www.nktechnologies.com
Power Supply
24U 24VAC /DC
@ 135 VAC
Single Pole Double Throw (SPDT or
Form C) relay
INSTRUCTIONS
DS3 SERIES
DC Current Operated Switch
Quick "How To" Guide
1. Run the wire you are monitoring through aper-
ture.
2. Mount the sensor.
3. Connect power & output wiring.
A. Make sure power supply matches specifications.
B. Make sure output load matches the output shown
on the sensors' label.
4. Adjust Setpoint
A. Chose correct range by positioning the Range
Jumper
B. Use the potentiometer to adjust the setpoint.
DS3Inst. Rev 3.2, 2/03 P/N 39-300-0101

Advertisement

loading

Summary of Contents for NK TECHNOLOGIES DS3 Series

  • Page 1 1. Run the wire you are monitoring through aper- RANGE RANGE ture. SOLID CORE JUMPER 5 SEC. CONTINUOUS Other NK Technologies Products Include: 2. Mount the sensor. AC & DC Current Transducers 4-20 A At least 200% At least 3. Connect power & output wiring. 10-50 A...
  • Page 2 Description Setpoint Adjustment DS3 Series are solid-state DC current operated switches. Power Supply Isolated Relay Output Isolated Solid State Output Range & Setpoint They operate (switch) when the current level through the 24VAC/DC (Shown De-Energized) (Shown De-Energized) DS3 switches have two setpoint adjustment mechanisms: hole exceeds the adjustable setpoint.